INSTALLING OPTIONAL LUG ADAPTER BUSBAR KITS
Procedure
1) Refer to Figure 2-4 to install the optional lug adapter busbar kits.
P/N 545405
P/N 545404
P/N 545571
1. Open the shelf’s front door.
2. Install the lug adapter busbar kits as shown.
Apply anti-oxidizing compound to busbar
mating surfaces before installing.
3. Torque connections to 58 in-lbs using the
supplied 1/4” hardware.
4. Close the front door after wiring is complete.
Top Cover Removed in
Illustration for Clarity Only
584622100 / 584622200 shown.
584622300 / 584622400 similar.
Figure 2-4
Installing Optional Lug Adapter Busbar Kits