Emerson Fluid Chiller Guía para resolver problemas Pagina 67

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 72
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 66
63
Troubleshooting Solenoid Valves
ProblemCausesCorrective Action
Normally Closed Valve Will Not Open
-or-
Normally Open Valve Will Not Close
Movement of plunger or diaphragm restricted
a) Corroded parts
b) Foreign material lodged in valve
c) Dented or bent enclosing tube
d) Warped or distorted body due to improper
brazing or crushing in vice
Clean affected parts and replace parts as
required. Correct the cause of corrosion or source
of foreign materials in the system.
Improper wiring
Check electrical circuit for loose or broken
connections. Attach voltmeter to coil leads and
check voltage, inrush and holding currents
Faulty contacts on relays or thermostats
Check contacts in relays and thermostats. clean or
replace as required.
Voltage and frequency rating or solenoid coil not
matched to electrical supply:
a) low voltage
b) high voltage
c) incorrect frequency
Check volt
age and frequency stamped on coil
assembly to make certain it matches electrical
source. If it does not, obtain new coil assembly
with proper voltage and frequency rating:
a) Locate cause of voltage drop and correct.
Install proper transformer, wire size as needed. Be
sure all connections are tight and that relays
function properly.
b) Excessively high voltage will cause coil burnout.
Obtain new coil assembly with proper voltage
rating.
c) Obtain new coil assembly with proper frequency
rating.
Oversized Valve
Install correct sized valve. Consult extended
capacities tables.
Valve improperly assembled.
Assemble parts in proper position making certain
none are missing from valve assembly.
Coil Burnout
a) Supply voltage at coil too low (below 85% of
rated coil voltage)
b) Supply voltage at valve too high (more than
10% above coil voltage
rating)
c) Valve located at high ambient
d) Plunger restricted due to: corroded parts,
foreign materials lodged in valve, dented or bent
enclosing tube or warped or distorted body due to
improper brazing or curshing in vise
e) With valve closed, pressure difference across
valve is too high preventing valve from opening
f) Improper wiring. Inrush voltage drop causing
plunger to fail to pull magnetic field due to:
- Wiring the valve to the load side of the motor
starter
- Wiring the valve in parallel with another
appliance with high inrush current draw
- Poor connetions, especially on low voltage,
where connections should be soldered
- Wire size of electrical supply too small
g) Electrical supply (voltage and frequency) not
matched to solenoid coil rating
a) Locate cause of low voltage and correct (check
tran
sformer, wire size, and control rating)
b) Locate cause of high voltage and correct
(install proper transformer or service)
c) Ventilate the area from high ambient. Remove
covering from coil housing
d) Clean affected parts and replace as required.
Connect cause of corrosion or source of foreign
material in the system
e) Reduce pressure differential to less than
300psi
f) Correct wiring according to valve manufacturers'
instructions. Solder all low voltage connections.
Use correct wire size.
g) Check coil voltage and frequency to ensure
match to electrical service rating. Install new coil
with proper voltage and frequency rating.
ProblemCausesCorrective Action
Normally Closed Valve Will Not Close
-or-
Normally Open Valve Will Not Open
Diaphragm or plunger restricted due to: corroded
parts, foreign material lodged in valve, dented or
bent closing tube, or warped body due to
improper brazing or crushing in vise
Clean affected parts and replace parts as
required. Correct the cause of corrosion or source
of foreign materials in the system. Install a filter-
drier upstream of solenoid valve
Manual opening stem holding valve open
With coil de-energized, turn manual stem in
counter clockwise direction until valve closes
Closing spring missing or inoperativeRe-assemble with spring in proper position
Electrical feedback keeping coil energized, or
switch contacts not breaking circui t to coil
Attach voltmeter at coil leads and check for
feedack or closed circuit. Correct faulty
contacts
or wiring
Reverse pressures (outlet pressure greater than
inlet pressure), or valve installed backwards
Install check valve at valve outlet, or install with
flow arrow in proper direction
ProblemCausesCorrective Action
Valve Closes, But Flow Continues
(Seat Leakage)
Foreign material lodged under seat Clean internal parts and remove foreign material
Valve seat damaged Replace valve or affected parts
Synthetic seat materials chippedReplace valve or affected parts
Valve improperly applied or assembledReplace valve with proper valve or re-assemble
Vista de pagina 66
1 2 ... 62 63 64 65 66 67 68 69 70 71 72

Comentarios a estos manuales

Sin comentarios