Temperature-Pressure Controls
Emerson Climate Technologies
Setpoints
PS1/PS2 are adjustable controls with external ad-
justment spindles for range and differential. Note that
manual reset controls have a xed differential and no
differential spindle. By turning the range spindle, the
upper setpoint is dened and by adjusting the differential
spindle, the differential and the lower setpoint is dened.
The dependency between upper and lower setpoint is
always as follows:
lower setpoint = upper setpoint – differential
The following two rules should be kept in mind:
➯ an adjustment of the range spindle always affects
both upper and lower setpoint.
➯ an adjustment of the differential spindle affects the
lower setpoint, only.
The controls are equipped with display scale and point-
ers to show the approximate settings. The display scales
are printed in relative pressure units “bar” and “psi”. For
precise setting of the controls, external gauges must be
used.
Contact Function
Contacts on Single Pressostats, PS1 are labeled
1-2-4 where ‘1’ refers to the common pole, ‘2’ refers to
the lower setpoint and ‘4’ refers to the upper setpoint.
This is true for all types of controls, irrespective whether
they are low pressure controls, high pressure controls,
manual or automatic reset types.
The contact function for automatic and manual reset
versions is as described below.
Automatic Reset
When pressure rises above the upper setpoint,
contacts 1-2 open and contacts 1-4 close. On decreas-
ing temperature lower setpoint contacts 1-4 open and
contacts 1-2 close.
Automatic reset contact function
Manual Reset Low Pressure
When pressure drops below the lower setpoint,
contacts 1-4 open, contacts 1-2 close and latch. Only
on pressure rise above upper setpoint and after press-
ing the manual reset button contacts 1-2 will open and
contacts 1-4 will close again.
Manual reset low pressure contact function
Manual Reset High Pressure
When pressure rises above the upper setpoint,
contacts 1-2 open, contacts 1-4 close and latch. Only on
falling pressure below lower setpoint and after press-
ing the manual reset button, contacts 1-4 will open and
contacts 1-2 will close again.
Manual reset high pressure contact function
For operational safety, all PS1/PS2 with manual
reset are designed as trip-free controls, i.e. pressing the
manual reset button while the pressure has not reached
its reset threshold will not operate the electrical contacts.
As Dual Pressostats PS2 have two sets of contacts,
their function is the same as on Single Pressostats PS1
with the only difference that the contact labels are pre-
ceded by an additional index. One side of the control is
labeled 11-12-14 and the second side is 21-22-24.
The contact function of controls with convertible reset
is as described above but depends on the position of the
convertible reset toggle, i.e. automatic or manual reset
position.
2
4
1
2
4
1
2
4
1
P
P
P