Emerson Fluid Chiller Guía para resolver problemas Pagina 29

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 72
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 28
25
Solenoid Valves
Emerson Climate Technologies
Installation
Solenoid Valves having a spring loaded piston or dia-
phragm may be installed and operated in any position,
but installing more than 90° from vertical is not recom-
mended since dirt or debris may collect in the solenoid
area and prevent it from operating. An adequate strainer
or lter drier should be installed ahead of each solenoid
valve to keep scale, pipe dope, solder, and other foreign
matter out of the valve.
When installing a solenoid valve, be sure the arrow
on the valve body points in the direction of refrigerant
ow.
When brazing valves with extended solder type con-
nections do not use too hot a torch and point the ow
away from the valve. These valves do not normally need
to be disassembled before installation; if the valve does
not have extended connections, disassemble the valve
before brazing. Wet rags or chill blocks are recom-
mended during brazing. They are needed to keep the
valve body cool so that body distortion on close-coupled
valves will not occur. Allow the valve body to cool before
replacing the valve’s operating insides to ensure that the
seat material and gaskets are not damaged by the heat.
When reassembling, do not over torque.
Application Overview
Application Product Family
Liquid, Suction Line Service 240RA/540RA
or Hot Gas By-Pass 50RB
100RB
200RB/500RB
Pressure Differential Valve for Gas Defrost 710RA
713RA
Emerson Solenoid Valves
Emerson offers a complete line of refrigerant solenoid
valves for refrigeration and air-conditioning applications.
As part of Emerson’s commitment to the industry, each
valve undergoes stringent Emerson testing to ensure
fail-safe operation. And, with the lowest external leak
rates in the industry, Emerson solenoid valves ensure
precise refrigerant ow, preventing system failures and
aiding in environmental protection.