Instruction Manual
D103621X012
4320 Position Monitor
April 2014
8
Table 4. Device Variables
INDEX
DEVICE VARIABLE
DESCRIPTION
DD Published To Gateway
(1)
0 Position PERCENT_OF_SPAN Travel (% of Calibration Output Span)
1 Closed/Low Limit Switch CLOSED_TRIGGER Reports Closed/Low condition (1 = Tripped, 0 = Not Tripped)
2 Opened/High Limit Switch OPEN_TRIGGER Reports Opened/High condition (1 = Tripped, 0 = Not Tripped)
3 Temperature DEVICE_TEMPERATURE Electronics Module Temperature (Degrees C)
4 Supply Voltage BATTERY_VOLTAGE Power Supply Output (Volts DC)
5 Set Point (on/off control only) SET_POINT Set Point (1 = Closed, 2 = Open)
6 Switch States SWITCH_STATE
Combines information in variables 1
and 2
(0 = Part Open, 1 = Closed,
2 = Opened, 3 = Unknown,
4 = Mid, 5 = High, 6 = Low)
7 Last Close Stroke Time CLOSE_STROKE_TIME Time the on/off controller took to previously close the valve
8 Last Open Stroke Time OPEN_STROKE_TIME Time the on/off controller took to previously open the valve
9 Timestamp 0 MESSAGE_0_TIMESTAMP Timestamp of burst message 0
10 Timestamp 1 MESSAGE_1_TIMESTAMP Timestamp of burst message 1
11 Timestamp 2 MESSAGE_2_TIMESTAMP Timestamp of burst message 2
12 Opened/High Dwell OPEN_DWELL_TIME The time the state has been/previously was in the open state.
13 Closed/Low Dwell CLOSED_DWELL_TIME The time the state has been/previously was in the closed state.
14 Transition Dwell PARTIALLY_OPEN_DWELL_TIME The time the state has been/previously was in the partially open state.
15 Cycle Counter CYCLE_COUNTS Cycle counted by the device
16 Scaled Position 16
Variable that can be configured to present the normalized (%) Position
signal in engineering units.
243 Battery Life Remaining BATTERY_LIFE Estimated battery life remaining
(days) - meaningless with
External Power option
244 PV % Range PERCENT_RANGE Copy of Variable 0 (%)
245 Loop Current CURRENT Always Indeterminate (not a number) (mA)
INDEX
DISCRETE VARIABLES
DESCRIPTION
DD Published To Gateway
0 Discrete Switch State DISCRETE_SWITCH_STATE Current state of the switch variable
(6 = Closed, 17 = Opening,
18 = Closing, 46 = Opened
48 = Unknown, 52 = Part-Open,
53 = Mid, 54 = High, 55 = Low)
1
Discrete Set Point
(On/Off Control only)
DISCRETE_SET_POINT Target value for the controlled variable
(4 = Close, 5 = Open,
6 = Closed, 46 = Opened)
1. 1410 gateway version 4.4.28 or later or 1420 gateway version 4.4.15 or later is required.