Resetting Power Module Variables
When power modules are replaced, you must reset Battery Life Remaining (shown in figure 37), which can be used for
scheduling maintenance of the power module. The counter can be reset using a Field Communicator or AMS Device
Manager. Resetting this value will also change the Power Module Date.
Field Communicator
Select Online, Configure, Manual Setup, Power Module, then Reset Module Data to reset Battery Life. Refer to the
Configure menu tree shown in figure 25.
Note
Reset Module Date can also be accessed by selecting Service Tools, Maintenance, and Power Module.
AMS Wireless Configurator or AMS Device Manager
In AMS Device Manager select Configure, Manual Setup, then select Reset Power Module Variables from the Power tab, as
shown in figure 37, to reset the power module variables.
Figure 37. Resetting Power Module Variables
SELECT
RESET POWER
MODULE VARIABLES
BATTERY LIFE
REMAINING
POWER MODULE DATE (INDICATES
DATE OF POWER MODULE INSTALLATION)
1. A warning will be displayed, noting this should only be done when a new power module is installed. Select Next if
you have replaced the power module. Select Cancel if the power module has not been replaced.
2. Select Yes when asked if you want to continue.
3. Press Next on the status screen displayed.