Instruction Manual
D103621X012
4320 Position Monitor
April 2014
55
Diagnostic Features
The 4320 includes the following diagnostics which can be accessed using the Field Communicator, AMS Wireless
Configurator or AMS Device Manager.
D Cycle counter is shipped from factory with a high value. This alert is used with valves that have service
recommendations based on number of actuation cycles. Reset Accumulated Count is used to clear the accumulated
count value. This is typically done when maintenance to valve and/or actuator has been performed. Refer to page
43 for additional information on Cycle Counter.
Refer to figure 25 and 26 for the Field Communicator menu trees.
In AMS Wireless Configurator or AMS Device Manager go to Configure, Alert Set‐up. Enter the Cycle Trip Point value on
the Cycle Counter tab to set the cycle counter. When the value turns yellow (indicating that a change has been made)
select Apply. Refer to figure 29.
To clear the accumulated cycle value select Reset Accumulated Count.
D Power status indicates the status of the power module voltage.
Refer to figure 25 and 26 for the Field Communicator menu trees.
In AMS Wireless Configurator or AMS Device Manager go to Service Tools, Variables, then select the Device tab to view
the power module voltage status. Refer to figure 30.
Figure 29. Resetting the Accumulated Count in AMS
Wireless Configurator and AMS Device Manager
ALERT SETUP
RESET
ACCUMULATED
COUNT
ENTER CYCLE TRIP
POINT
CONFIGURE
APPLY
Figure 30. Power Status in AMS Wireless
Configurator and AMS Device Manager
DEVICE TAB
SERVICE TOOLS
VARIABLES
POWER MODULE
VOLTAGE