Instruction Manual
D103621X012
4320 Position Monitor
April 2014
6
Table 1. Specifications (continued)
Wireless Classifications
Class A digital device, complies with part 15 of the
FCC Rules
Contains FCC ID: LW2RM2510
Contains IC: 2731A‐RM2510
Electromagnetic Compatibility
Meets EN 61326‐1 (First Edition)
Immunity—Industrial locations per Table 2 of
the EN 61326‐1 standard. Performance is
shown in table 2 below.
Emissions—Class A & B. Performance is shown in
table 3 below.
ISM equipment rating: Group 1, Class A & B
Vibration Testing
Meets or exceeds vibration levels specified in
ANSI/ISA 75.13.01 1996 (2007):
4 mm peak to peak at 5 Hz,
2 g from 15150 Hz, and
1 g from 150 2000 Hz
European Directive Information
This product complies with the following directives:
ATEX Directive (94/9/EC)
Electro Magnetic Compatibility (EMC) (2004/108/EC)
Radio and Telecommunications Terminal Equipment
Directive (R&TTE) (1999/5/EC)
Refer to the Safety Instructions (D103022X012) for
the Declaration of Conformity
Operating Temperature Limits
(2)(3)
Monitoring
Battery Power: -40 to 85_C (-40 to 185_F)
External Power: -40 to 80_C (-40 to 176_F)
LCD may not be readable below -20_C (-4_F)
With Pneumatic Output (On/Off Control):
-20 to 50_C (-4 to 122_F)
Temperature Sensitivity
0.06% change per degree C
Storage Temperature Limits
(2)(3)
-40 to 70_C (-40 to 158_F)
Humidity Limits
10-95% Non‐Condensing Relative Humidity
Electrical Classification
CSA (C/US)— Intrinsically Safe
ATEX— Intrinsically Safe
IECEx— Intrinsically Safe
Refer to Hazardous Area Classifications and Special
Instruction for “Safe Use” and Installations in
Hazardous locations, starting on page 15, for
additional information
Electrical Housing
Type 4X, IP66 & IP67
IEC 61010 Compliance
Meets Pollution Degree 2
Adjustments
Zero and Maximum Span through local interface
Weight
Monitoring— 0.57 kg (1.25 lbs)
On/Off Control— 1.6 kg (3.4 lbs)
Power Module
(3)
Standard —Lithium, non‐rechargeable
Power Module Limits
(4)
Standard— 5 years at update rate of 16 seconds or
longer with 3 additional devices communicating
through it
Extended‐Life— 10 years at update rate of 8 seconds
or longer with 3 additional devices communicating
through it.
Shelf life— 10 years (radio off)
External Power (Optional)
12 - 28 volts DC
100 mA maximum operating current
Polarity Insensitive
Wire Size—14-20 gauge
‐continued‐