Instruction Manual
D103621X012
4320 Position Monitor
April 2014
16
ATEX II 1 G
IECEx
Intrinsically Safe
Monitor Version
Battery Sourced Power Module w/out Pneumatic Output External Power w/out Pneumatic Output
Ex ia IIC T3/T4/T5 Ga Ex ia IIC T5 Ga
Install per control drawing GE59530 Install per control drawing GE59530
as shown in figure 8 and 9 as shown in figure 8 and 10
Enclosure: Type 4X, IP66 & IP67 Enclosure: Type 4X, IP66 & IP67
T3(Tamb ≤ 85_C), T4(Tamb ≤ 75_C), T5(Tamb ≤ 40_C) T5(Tamb ≤ 80_C)
Temperature Range: -40_C to 85_C Temperature Range: -40_C to 80_C
Control Version
Battery Sourced Power Module with Pneumatic Output External Power with Pneumatic Output
Ex ia IIC T4/T5/T6 Ga Ex ia IIC T5 Ga
Install per control drawing GE59530 Install per control drawing GE59530
as shown in figure 8 and 9 as shown in figure 8 and 10
Enclosure: Type 4X, IP66 & IP67 Enclosure: Type 4X, IP66 & IP67
T4(Tamb ≤ 50_C), T5(Tamb ≤ 46_C), T6(Tamb ≤ 31_C) T5(Tamb ≤ 50_C)
Temperature Range: -20_C to 50_C Temperature Range: -20_C to 50_C
ATEX Special Conditions of Use
The apparatus shall not be subjected to mechanical impacts or friction.
The piezo valve can be used with natural gas as control fluid provided that no gas-air mixtures are present in the
pressure system.
The apparatus must be only connected to certified intrinsic safety equipment and this combination must be
compatible regarding intrinsic safety rules.
Battery Sourced Power Module:
The apparatus can only be powered with a module type GE57654X012 or GE57655X012
External Power:
The apparatus may be powered externally via external power module GE61615X012
IECEx Special Conditions of Use
The apparatus shall not be subjected to mechanical impacts or friction.
The piezo valve shall be used for control of nonflammable medium only.
The apparatus must be only connected to a certified intrinsically safe equipment and this combination must be
compatible regarding intrinsic safety rules:
Battery Sourced Power Module:
The apparatus can only be powered with a module type GE57654X012 or GE57655X012
External Power:
The apparatus may be powered externally via external power module GE61615X012