Vista de pagina 44
Instruction Manual
D103621X012
4320 Position Monitor
April 2014
45
Mode Alerts
Device Not in Service—indicates the Set Point is not being applied to the process.
Output Fault State—indicates that the control output has been driven to the configured fault state.
Enable 'Out of Service'
Enable 'Fault State' Alert
Tracking Alerts
Note
Tracking Alerts are not available in snap-acting mode.
Valve Movement Fail—indicates the position feedback from the controlled equipment has not responded to the set
point command.
Valve Drift—indicates the valve has deviated from the set point.
Enable 'Movement Fail' Alert
Valve Timeout—defines the time allotted for achieving the set point before declaring a valve movement failure.
Enable 'Valve Drift'
Close Time Alerts
Note
Close Time Alerts are not available in snap-acting mode.
Close Stroke Time Alert—indicates that the last close action fell outside the time limits allowed by the configuration.
Close Stroke (Cal)—indicates the time required to complete close stroke during Auto Calibration.
Last Close Stroke—indicates the time required to complete the most recent stroke from opened to closed position.
Enable 'Close Stroke'
High Trip Point
Low Trip Point
Open Time Alerts
Note
Open Time Alerts are not available in snap-acting mode.
Open Stroke Time Alert—indicates that the last open stroke time fell outside the time limits allowed by the
configuration.
Vista de pagina 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 67 68