Site Preparation and Installation
22
Figure 12 Indoor water/glycol condensing unit electrical field connections
Field Supplied Unit Disconnect
Switch when Factory Unit
Disconnect Switch is not
Supplied.
Electric Service not
by Liebert
Optional Factory Installed
Disconnect Switch
Field Supplied 24V NEC Class 1 Wiring to
Fan/Coil Unit.
Field Supplied 24V NEC Class 1 Wiring to
Drycooler (Glycol cooled units only).
Line VoltageElectric Power Supply
Conduit Voltage.
Connection Terminal for Field Supplied
Earth Grounding Wire.
Low VoltageElectric Power
Supply Conduit Entrance
Field Supplied 24V NEC Class 1 Wiring
Between Glycol Condensing Unit
and Drycooler.
Remote Drycooler Connection.
Field Supplied 24V NEC Class 1
Wiring (Glycol cooled units only).
Removable Access Panel
Heat Rejection Connection. Field supplied
24V NEC class 2 wiring. See note 2. Wire
connections from evaporator module:
1. 24V GND
2. 24V Supply
3. High Pressure Alarm (OPT)
4. Hot Gas Bypass Connection
(only on units with Hot Gas Bypass)
NOTES:
1. Refer to specification sheet for full load amp. and wire size amp. ratings.
2. Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75’ (23m) or not
to exceed 1 volt drop in control line.
DPN000228_Rev0