Site Preparation and Installation
7
If the return air duct is short or if noise is likely to be a problem, sound-absorbing insulation should
be used inside the duct. Duct work should be fabricated and installed in accordance with local and
national codes.
Additional components such as a free-cooling coil, hot water reheat coil or high efficiency filters will
reduce available static pressure.
2.4.3 Piping Connections and Coolant Requirements
Drain Line
A 3/4 in. (19.1 mm) female pipe thread (FPT) connection is provided for the evaporator coil condensate
drain. This line also drains the humidifier, if applicable. The drain line must be located so it will not
be exposed to freezing temperatures. The drain should be the full size of the drain connection.
The evaporator drain pan includes a float switch to prevent unit operation if drain becomes blocked.
The optional condensate pump kit is required when the evaporator is installed below the level of the
gravity-fed drain line.
Humidifier Water Supply Line
Units supplied with the optional humidifier package have a 1/4 in. (6.4 mm) FPT connection for water
inlet. Supply pressure range is 10 psig to 150 psig. Required flow rate is 1 gpm. A shut-off valve
should be installed in this line to isolate the humidifier for maintenance.
Chilled Water Piping—On chilled water units install manual service shut-off valves at the supply
and return lines of each unit. These shut-off valves are used for routine service or emergency isolation
of the unit.
Chilled water supply and return lines must be insulated. Insulating them will prevent condensation
of the water supply and return lines to the unit.
The minimum recommended water temperature is 42°F. Connection sizes are 1 in. (25.4 mm) FPT.
Table 5 Evaporator external static pressure
Turns
Open
1.5 hp Motor (60hz) 2.0 hp Motor (60hz)
Blower
rpm
External
Static, in.
Blower
rpm
External
Static, in.
1n/a n/a 1329 n/a
1.5 n/a n/a 1296 n/a
2 1037 0.9 1264 n/a
2.5 1005 0.7 1231 1.5
3 972 0.6 1199 1.4
3.5 940 0.5 1164 1.3
4 907 0.4 1134 1.2
4.5 875 0.3 1102 1.1
5 843 0.2 1069 1.0
5.5 810 0.1 1037 0.9
6 778 0.0 1005 0.7
!
CAUTION
The drain line must not be trapped outside the unit or water may back up in drain pan. Drain
is internally trapped.
This line may contain boiling water. Use copper or other suitable material for the drain line.
NOTE
Do NOT route humidifier supply line in front of filter box access panel.