Introduction
1
1.0 INTRODUCTION
1.1 Product Description and Features
The Mini-Mate2
™
is a temperature/humidity control system designed to be installed above a ceiling
grid system. The unit is available as a split system evaporator to be matched with an Indoor Centrif-
ugal Condensing Unit, Outdoor Prop Fan Condensing Unit or Indoor Water/Glycol Condensing Unit.
A self-contained Chilled Water Fan Coil is also available.
1.1.1 Controls
The Mini-Mate2 system includes a wall-mounted display panel that includes a liquid crystal display
(LCD) screen and a 7 membrane keypad. The control is menu-driven for ease of use. Figure 17
depicts the complete menu tree for the control. All control setpoints and alarm setpoints are program-
mable.
1.1.2 Evaporator System Components
DX Evaporator Section
The evaporator section includes the evaporator coil, thermostatic expansion valve, filter dryer and
blower. The evaporator coil is constructed of copper tubes and aluminum fins and is designed for the
high sensible heat ratio required for electronic equipment. Room air circulation is accomplished by a
double inlet, belt driven centrifugal blower that has been dynamically balanced. The blower motor
has self-aligning bearings and lifetime lubrication.
Chilled Water Model
The Chilled Water model is self-contained and is designed for use with an existing chilled water loop.
It contains a chilled water coil and a slow open/close valve or optional modulating valve to control the
flow of chilled water.
1.1.3 Condensing Unit Components
The condensing unit is connected to the evaporator unit by two refrigerant lines and a low voltage
control wire. The condensing unit requires a power source and a power disconnect switch. A single
point power kit is available for close-coupled units.
Air Cooled Condensing Unit (Indoor Centrifugal)
The Air Cooled Condensing units (MC models) include: scroll compressor with crankcase heater, high
pressure switch, condenser coil and Lee-Temp head pressure control with receiver.
Air Cooled Condensing Unit (Outdoor Prop Fan)
Outdoor Air Cooled Condensing Units (PFC models) include: scroll compressor with crankcase heater,
high pressure switch, condenser coil, filter dryer, propeller fan and Lee-Temp head pressure control
with receiver.
Water/Glycol Condensing Unit (Indoor)
The Water/Glycol Cooled Condensing units include: scroll compressor with crankcase heater, high
pressure switch, coaxial condenser and regulating valve. Drycooler and pumps are selected separately
for glycol systems.
1.2 Optional Equipment
1.2.1 Canister Humidifier
The optional, factory-installed steam generating humidifier adds pure water vapor to the room air to
control humidity. Room humidity setpoints are established by the user. The humidifier components
include a steam canister (replaceable), control board, inlet strainer, fill and drain valves.
1.2.2 Electric Reheat
The reheat feature is energized when required to heat room air or to control room temperature during
dehumidification. A safety switch prevents the reheat from exceeding temperature limits.