Site Preparation and Installation
4
2.1.2 Location Considerations
Locate the evaporator unit over an unobstructed floor space if possible. This will allow easy access for
routine maintenance or service. Do not attach additional devices (such as smoke detectors, etc.) to the
housing, as they could interfere with the maintenance or service.
Figure 1 Air cooled systems
Figure 2 Water/glycol cooled systems
!
CAUTION
Units contain water. Water leaks can cause damage to sensitive equipment below. DO
NOT MOUNT UNITS OVER SENSITIVE EQUIPMENT. A field supplied pan with drain
must be installed beneath cooling units and water/glycol cooled condensing unit.
NOTE
Do NOT mount units in areas where normal unit operating sound may disturb the working
environment.
NOTE
Temperature and humidity sensors are located in the wall box. Carefully select a position
for the box where discharge air DOES NOT directly blow on the sensors.
Split System Evaporator
Supply & Return Air Ducted
Outdoor Prop Fan Condensing Unit
Split System Evaporator
Supply & Return Air Ducted
Indoor Air Cooled Condensing Unit
Evaporator
Prop Fan
Condensing Unit
Evaporator
Centrifugal Fan
Condensing Unit
Split System Evaporator
Supply & Return Air Ducted
Remote Water/Glycol Condensing Unit
Evaporator
Evaporator
Cooling
Tower
Water/Glycol
Condensing Unit
Water/Glycol
Condensing Unit
Split System Evaporator
Supply & Return Air Ducted
Remote Water/Glycol Condensing Unit
Drycooler