Accuracy Example
When using a Pt 100 (α = 0.00385) sensor input with a 0 to 100 °C span: Digital
accuracy would be ±0.15 °C, D/A accuracy would be ±0.03% of 100 °C or ±0.03 °C,
Total = ±0.18 °C.
DIN
Typ e U
DIN 43710 –200to
600
–328to
1112
25 45 ± 0.35 ± 0.63 ±0.03% of
span
Typ e
W5Re/
W26Re
ASTM E 988–96 0to
2000
32 to
3632
25 45 ±0.70 ±1.26 ±0.03% of
span
Millivolt
Input
–10 to 100 mV 3 mV ±0.015 mV ±0.03% of
span
2-, 3-, 4-Wire Ohm Input
0 to 2000 ohms 20 ohm ±0.45 ohm ±0.03% of
span
(1) No minimum or maximum span restrictions within the input ranges. Recommended minimum span will hold
noise within accuracy specification with damping at zero seconds.
(2) Digital accuracy: Digital output can be accessed by HART Communicator or Rosemount control system.
(3) Total Analog accuracy is the sum of digital and D/A accuracies.
(4) Total digital accuracy for thermocouple measurement: sum of digital accuracy +0.5 °C
(5) Digital accuracy for NIST Type B T/C is ±3.0 °C from 100 to 300 °C.
(6) Digital accuracy for NIST Type K T/C is ±0.70 °Cfrom–292 to –130 °F(–180 to –90 °C).
Sensor
Options
Sensor Reference Input Ranges
Recommended
Min. Span
(1)
Digital
Accuracy
(2)
D/A
Accuracy
(3)