Rail Mount Transmitter with Integral Mount Sensor
Refer to Volume 2 of the Rosemount Sensors Product Data Sheet (document
number 00813-0101-2654) for complete sensor and mounting accessory
information.
To complete the assembly, follow the procedure described below.
1. Attach the transmitter to a suitable rail or panel.
2. Attach the thermowell to the pipe or process container wall. Install and
tighten the thermowell before applying pressure.
3. Attach the sensor to the connection head and mount the entire assembly to
the thermowell.
4. Attach sufficient lengths of sensor lead wire to the sensor terminal block.
5. Attach and tighten the connection head cover. Enclosure covers must be fully
engaged to meet explosion-proof requirements.
6. Run sensor lead wires from the sensor assembly to the transmitter.
7. Set the transmitter failure mode switch (see Figure 2-11 on page 2-11).
8. Attach the sensor and power leads to the transmitter. Avoid contact with
leads and terminals.
Figure 2-6. Typical Rail Mount Transmitter Mounting Configuration Using
Integral Mount Sensor and Assembly
Integral Mount Sensor
with Terminal Block
Connection Head
Standard Extension
Threaded Thermowell
Rail Mount Transmitter
Sensor Leads
with Cable Gland
644-0000C04A