2-8
EN
Rosemount Inc
Rail Mount Transmitter with Threaded Sensor
Refer to Volume 1 of the Rosemount Sensors Product Data Sheet (document
number 00813-0100-2654) for complete sensor and mounting accessory
information.
To complete the assembly, follow the procedure described below.
1. Attach the transmitter to a suitable rail or panel.
2. Attach the thermowell to the pipe or process container wall. Install and
tighten the thermowell before applying pressure.
3. Attach necessary extension nipples and adapters. Seal the nipple and adapter
threads with silicone tape.
4. Screw the sensor into the thermowell. Install drain seals if required for severe
environments or to satisfy code requirements.
5. Screw the connection head to the sensor.
6. Attach the sensor lead wires to the connection head terminals.
7. Attach additional sensor lead wires from the connection head to
the transmitter.
8. Attach and tighten the connection head cover. Enclosure covers must be fully
engaged to meet explosion-proof requirements.
9. Set the transmitter failure mode switch (see Figure 2-11 on page 2-11).
10. Attach the sensor and power leads to the transmitter. Avoid contact with leads
and terminals.
Figure 2-7. Typical Rail Mount Transmitter Mounting Configuration Using
Threaded Style Sensor and Assembly
Rail Mount
Transmitter
Threaded
Style Sensor
Threaded
Thermowell
Standard Extension
Threaded Sensor
Connection Head
644-0000A04B