TABLE 4-2. Hardware diagnostic messages
Symptom
Potential
Source
Corrective Action
Transmitter
Does Not
Communicate
with HART
Communicator
Loop Wiring
Check the revision level of the transmitter device descriptors
(DDs). The communicator should report Dev v5, DD v2.
Check for a minimum of 250 ohms resistance between the
power supply and HART-based communicator connection.
Check for adequate voltage to the transmitter. If a HART-
based communicator is connected and 250 ohms resistance
is in the loop, the transmitter requires a minimum of 12.0 V at
theterminalstooperate(overentire3.75to23mA
operating range).
Check for intermittent shorts, open circuits, and multiple
grounds.
Specify the transmitter by tag number. For certain non-
standard transmitter installations, specify the transmitter tag
number to initiate communications.
High Output
Sensor Input
Failure or
Connection
Connect a HART-based communicator and enter the
Transmitter test mode to isolate a sensor failure.
Check for a sensor open or short circuit.
Check the process variable to see if it is out of range.
Loop Wiring
Check for dirty or defective terminals, interconnecting pins,
or receptacles.
Power
Supply
Check the output voltage of the power supply at the
transmitter terminals. It should be 12.0 to 42.4 V dc (over
entire 3.75 to 23 mA operating range).
Electronics
Module
Connect a HART-based communicator and enter the
transmitter status mode to isolate module failure.
Connect a HART-based communicator and check the sensor
limits to ensure calibration adjustments are within the sensor
range.
Erratic Output
Loop Wiring
Check for adequate voltage to the transmitter. It should be
12.0 to 42.4 V dc at the transmitter terminals (over entire
3.75 to 23 mA operating range).
Check for intermittent shorts, open circuits, and multiple
grounds.
Connect a HART-based communicator and enter the Loop
test mode to generate signals of 4 mA, 20 mA, and user-
selected values.
Electronics
Module
Connect a HART-based communicator and enter the
Transmitter test mode to isolate module failure.