Rosemount 3051S Series
Overpressure Limits Transmitters withstand the following limits without damage:
Coplanar Sensor Module (Single Variable)
In-Line Sensor Module
Liquid Level Transmitter (3051S_L)
Overpressure limit is dependent on the flange rating or sensor rating (whichever is lower). Use
Instrument Toolkit to ensure the seal system meets all pressure and temperature limits.
Static Pressure Limits Coplanar Sensor Module (Single Variable)
Operates within specifications between static line pressures of:
Burst Pressure Limits Coplanar Sensor Module (3051S_C)
10000 psig (689,5 bar)
In-Line Sensor Module (3051S_T)
• Ranges 1-4: 11000 psi (758,4 bar)
• Range 5: 26000 psi (1792,64 bar)
Range
DP
(1)
& GP
(1) The overpressure limit of a DP Sensor with the P9 option is 4500
psig (310,3 bar). The overpressure limit of a DP Sensor with the
P0 option is 6092 psig (420 bar).
AP
3051S_CD, 3051S_CG 3051S_CA
0 750 psi (51,7 bar) 60 psia (4,13 bar)
1 2000 psi (137,9 bar) 750 psia (51,7 bar)
2 3626 psi (250,0 bar) 1500 psia (103,4 bar)
3 3626 psi (250,0 bar) 1600 psia (110,3 bar)
4 3626 psi (250,0 bar) 6000 psia (413,7 bar)
5 3626 psi (250,0 bar) N/A
Range
GP AP
3051S_TG 3051S_TA
1 750 psi (51,7 bar)
2 1500 psi (103,4 bar)
3 1600 psi (110,3 bar)
4 6000 psi (413,7 bar)
5 15000 psi (1034,2 bar)
Range
DP Sensor
(1)
(1) The static pressure limit of a DP Sensor with the P9 option is 4500
psig (310,3 bar). The static pressure limit of a DP Sensor with the
P0 option is 6092 psig (420 bar).
3051S_CD
0 0.5 psia to 750 psig (0,03 to 51,71 bar)
1 0.5 psia to 2000 psig (0,03 to 137,9 bar)
2 0.5 psia to 3626 psig (0,03 to 250 bar)
3 0.5 psia to 3626 psig (0,03 to 250 bar)
4 0.5 psia to 3626 psig (0,03 to 250 bar)
5 0.5 psia to 3626 psig (0,03 to 250 bar)