7
2. Installation Instructions
Emerson Climate Technologies, Inc. requires that all
customers review the recommended guidelines in the
published Application Engineering Bulletins, and
ensure that best engineering practices are followed in
the use of Copeland® brand compressors. Emerson
Climate Technologies, Inc. Application Engineering
Bulletins can be found on our website,
EmersonClimate.com under the section titled “Online
Product Information”. The advice and conclusion by
Emerson Climate Technologies, Inc. represents our
best judgment under the circumstances, but such
advice given and/or conclusion made, or results
obtained shall be deemed used at your sole risk.
2.1 Mounting and Installation
The Intelligent Store™ Discus® compressor is
designed and engineered for use in a supermarket
rack application. Its environmental restrictions are no
different than other Copeland® brand Discus
®
com-
pressors. As such, the compressor must be in an
equipment room, rack house or roof enclosure to pre-
vent direct precipitation on the compressor.
The following clearance provisions must be
considered when designing the rack for use with an
Intelligent Store™ Discus® compressor:
• Removal of the Intelligent Store™ Discus®
front cover for access to the RS485 communi-
cations network connection.
• Removal of the Intelligent Store™ Discus®
front box for service reasons.
• Opening of the side enclosure (2D / 3D
compressors) for service and for communica-
tions cable routing.
• Removal of the terminal box and harness
shroud (4D compressors) for service and
communications cable routing.
Refer to Emerson Climate Technologies, Inc. cus-
tomer drawings in Appendix D for dimensional
envelopes of Intelligent Store™ Discus® compres-
sors.
2.2 Terminal Box Connections
The following terminal box connections must be made
by the original equipment manufacturer:
• Module Power - 230 VAC to power the
Intelligent Store™ Discus® electronics, acces-
sories (e.g., unloader coils or injection valves)
and contactor coil.
• Contactor - Output connections to the contac-
tor coil.
• Crankcase Heater - 230 VAC power for the
crankcase heater, such as from the auxiliary
contact on the compressor contactor. Leave
connectors empty when crankcase heaters
are not included.
• Intelligent Store™ Discus® and Discus® com-
pressors use the same motor terminal con-
nections.
All terminal box connections are to be made with AMP
P/N 2-520183-2 or equivalent. Refer to figure 2.1.
Figure 2.1 3D Terminal Box Assembly
Feature
Electrical
Requirements
Intelligent Store™ Discus®
Supply Voltage
(Module Power)
208/230 volts
170 volts min
Pilot Circuit Voltage
(Contactor Output)
208/230 volts
170 volts min (supplied by
Intelligent Store™ Discus®)
Crankcase Heater 208/230 Volts
Compressor Motor Model Dependent
Variable Speed
Compatibility
Not Compatible with
Variable Speed
Head Fan Per OEM Wiring
Comentarios a estos manuales