Sample Rack with Intelligent Store™ Discus®
Compressors
Figure 3.31 Suction Group Setup Screen (Comp
Outs)
3.19 Welded Contactor
This protection feature is designed to prevent
damage to the motor in the event of a welded
contactor. Once a welded contactor is sensed by the
module, the rack controller will issue a command to
pull the contactor in and keep the compressor
running until it can be serviced. Refer to section 1.2.4
of this document for more detailed information on this
protection feature. To enable welded contactor
protection, follow these steps:
1. Press menu to open the Main Menu.
2. Press 1 (Suction Groups).
3. Highlight the appropriate suction group and press
F5 (Setup).
4. Press Cntrl + 0 to access the Additional Tabs
Menu.
5. Press J (Welded Contact).
6. Input the appropriate Controller / Application /
Property using F4 (Lookup).
Once the Welded Contactor associations have been
made, the suction group setup screen should look like
figure 3.32 below:
Figure 3.32 Welded Contactor Setup Screen
3.20 Proofing
Proofing verifies that the compressor is turning ON
and OFF as commanded by the E2 rack controller.
This is accomplished by comparing the run command
status from the E2 with the built in proof checking
output of the module. In the event that a compressor
fails proofing, the E2 can call on another compressor
to satisfy demand. To enable proofing, follow these
steps:
1. Press menu to open the Main Menu.
2. Press 1 (Suction Groups).
3. Highlight the appropriate suction group and press
F5 (Setup).
4. Press F2 (Next Tab) until the Comp Setup tab is
highlighted.
5. Select Yes under the Proof column (see figure
3.33).
6. Press F2 (Next Tab) until the More tab is
highlighted.
Note: The COMP RUN PROOF selection will not be
displayed on the Suction Group Setup screen unless
proofing has been enabled by selecting Yes under the
Proof column on the Comp Setup tab.
- 25° Suction - 15° Suction
4DL3A150L-TSK
04I35625R
3DRHA100E-TFD
04I00300R
4DS3A220E-TSK
04I35631R
3DRHA100E-TFD
04I00439R
2DC3-050E-TFD
04I00435R
Subnet: 15
Node: 2
Subnet: 15
Node: 5
Subnet: 15
Node: 4
Subnet: 15
Node: 3
Subnet: 15
Node: 1
RACK1COMP1 RACK1COMP2 RACK1COMP3 RACK2COMP1 RACK2COMP2
Comp1
Address
Compressor
Name
Stages
Comp2
Comp3
(unloader)
Comp4
Comp5
(unloader)
Comp1
Comp2
(unloader)
Comp3
AE8-1337 R1