18
3.10 Intelligent Store™ Discus®
Commissioning Procedure for E2
Firmware Revisions 2.07 through 2.20
Each Intelligent Store™ Discus® Compressor module
(referred to as “CST” in the E2) is connected to the E2
via the RS-485 communications network. As with
other devices, the module must first be “commis-
sioned” to establish communications with the rack
controller. During this commissioning process the E2
will designate a specific subnet and node address for
each module (front control box) that is connected. It
will also upload and store a master record of the
model number, serial number, and programmable set-
tings from each module.
Warning: E2 programs from a previously commis-
sioned store should not be transferred to the new
E2 to short-cut the commissioning process.
The commissioning process can be broken down into
the following steps:
1. Node Recovery
2. Configuring Applications
a. Module Renaming
b. Suction Pressure Mapping
c. Setting Failsafe Mode
3. Suction Group Setup
a. Suction Group Associations
b. Welded Contactor Setup
c. Compressor Run Proofing
There are two main menus that must be accessed to
perform module commissioning. These are the CST
Network Status screen and the CST Setup screen. To
access these screens, refer to figures 3.17 and 3.18
below:
Figure 3.17 CST Network Status screen navigation (Key sequence 7-7-1)
Figure 3.18 CST Setup screen navigation (Key sequence 5-35)