Emerson 1410 Manual de servicio Pagina 139

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 222
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 138
FRU Information and Sensor Data Records
AXP 1410 Installation and Use (6806800H70D)
139
Table 7-20 Sensor No. 15 Fan 2 Outlet
Feature Raw Value/Description Interpreted Value
Sensor Name Fan 2 Outlet
Device
Sensor Type 0x04 Fan
Class 0x01 Threshold
Sensor Owner LUN 0x00
Entity ID 0x1D Cooling Unit
Entity Instance 0x63
Rearm mode Auto
Hysteresis support Readable/Settable
Threshold access support Readable/Settable
Event message control Entire Sensor only
Readable threshold mask,
Settable threshold mask (bytes
19, 20)
0x3F3F Upper and Lower Non-Critical, Critical
and Non-Recoverable Thresholds are
Readable and Settable
Reading Type Unsigned
Lower Non-Critical, Critical and
Non-Recoverable thresholds
0x24, 0x24, 0x24 (902, 902, 902) RPM
Upper Non-Critical, Critical and
Non-Recoverable thresholds
0xCE, 0xE6, 0xF2 (5588, 5610, 5610) RPM
Table 7-21 Sensor No. 16 Fan 3 Outlet
Feature Raw Value/Description Interpreted Value
Sensor Name Fan 3 Outlet
Device
Sensor Type 0x04 Fan
Class 0x01 Threshold
Sensor Owner LUN 0x00
Entity ID 0x1D Cooling Unit
Vista de pagina 138
1 2 ... 134 135 136 137 138 139 140 141 142 143 144 ... 221 222

Comentarios a estos manuales

Sin comentarios