Supported Modbus Points
37
Table 25 Liebert DS - Input and Holding Registers
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Note
Humidifier Run Hours Threshold 30073 40073
-
1 Hour
Dehumidification Run Hours Threshold 30074 40074
-
1 Hour
CW/FC Run Hours Threshold 30075 40075
-
1 Hour
Electrical Heaters #1 Run Hours
Threshold
30076 40076
-
1 Hour
Electrical Heaters #2 Run Hours
Threshold
30077 40077
-
1 Hour
Electrical Heaters #3 Run Hours
Threshold
30078 40078
-
1 Hour
Hot Water / Hot Gas Run Hours
Threshold
30079 40079
-
1 Hour
Operating State
6
30100 -
-
1 -
Number of Active Events/Alarm 30101 -
-
- -
Summary Alarm Status
7
30102 -
-
- -
Fan Ramp 30103 -
-
1 %
Cooling Ramp 30104 -
-
1 %
Free Cooling Ramp 30105 -
-
1 %
Heating Ramp 30106 -
-
1 %
Humidification Ramp 30107 -
-
1 %
Dehumidifier Ramp 30108 -
-
1 %
FreeCooling Status
8
30109 -
-
1 %
Return Temperature 30110 -
-
x10 C°
Actual Temperature SP 30111 -
-
x10 C°
Supply Temperature 30112 -
-
x10 C°
Actual Supply Temperature SP 30113 -
-
x10 C°
FC Temperature 30115 -
-
x10 C°
Sensor A Temperature 30116 -
-
x10 C°
Sensor B Temperature 30117 -
-
x10 C°
Sensor C Temperature 30118 -
-
x10 C°
Digital Scroll Compressor 1 High
Temperature
30119 -
-
x10 C°
Digital Scroll Compressor 2 High
Temperature
30120 -
-
x10 C°
Return Humidity 30130 -
-
1 %
Actual Humidity SP 30131 -
-
1 %
Sensor A Humidity 30132 -
-
1 %
Sensor B Humidity 30133 -
-
1 %
Sensor C Humidity 30134 -
-
1 %
Fan Run Hour 30141 -
-
1 Hour
Compressor 1 Run Hour 30142 -
-
1 Hour
Compressor 2 Run Hour 30143 -
-
1 Hour
Comentarios a estos manuales