Supported Modbus Points
28
Table 20 Liebert Series 610
™
SCC UPS - Status and Coil
Data Point Status Coil Number of Bits Notes / Units
Auto Retransfer Primed 10049 - 1 -
Load On Inverter 10073 - 1 -
Load On Bypass 10074 - 1 -
Load On Bypass 10129 - 1 -
Manual Reset Transfer 10130 - 1 -
Emergency Transfer 10134 - 1 -
Output Switch open 10138 - 1 -
SBS Unable 10148 - 1 -
Output Frequency Off 10153 - 1 -
Output Overload 10154 - 1 -
System Emergency Off 10157 - 1 -
Input Power Supply Fail 10186 - 1 -
Input Phase Rotation Error 10191 - 1 -
Bypass Input Voltage Fail 10202 - 1 -
Output Under Voltage 10218 - 1 -
Output Over Voltage 10219 - 1 -
Module Alarm Active 10304 - 1 -
Customer Alarm 1 10313 - 1 -
Customer Alarm 2 10314 - 1 -
Customer Alarm 3 10315 - 1 -
Customer Alarm 4 10316 - 1 -
Customer Alarm 5 10317 - 1 -
Customer Alarm 6 10318 - 1 -
Customer Alarm 7 10319 - 1 -
Customer Alarm 8 10320 - 1 -