Supported Modbus Points
9
Table 9 Liebert NX - Input and Holding Registers
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale Notes / Units
Number of Input Lines 30004 40004 1 1 Bits 12 - 15
Number of Bypass Lines 30004 40004 1 1 Bits 4 - 7
Number of Output Lines 30004 40004 1 1 Bits 8 - 11
Number of SubModules 30009 40009 1 - -
Module Number 30014 40014 1 - -
Device Module Count 30015 40015 1 - -
Device Redundant Count 30016 40016 1 - -
Device Module Mode 30017 40017 1 - -
Nominal Power Rating 30021 40021 2 - VA
Nominal Input Voltage 30027 40027 1 - V
Nominal Output Voltage 30028 40028 1 - V
Nominal Static Bypass Switch
Voltage
30029
40029
1 - V
Nominal Input Frequency 30031 40031 1 10 Hz
Nominal Output Frequency 30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100 -
Nominal DC Bus #1 Voltage 30035 40035 1 - V
Nominal DC Bus #2 Voltage 30036 40036 1 - -
Nominal Battery Float Voltage 30038 40038 1 - V
Load Bus Sync Mode 30040 40040 1 - -
Auto Restart Delay 30051 40051 1 1 Seconds
Device Low Battery Time 30053 40053 1 - Minutes
Input Frequency 30107 - 1 10 Hz
Output Frequency 30108 - 1 10 Hz
Bypass Frequency 30109 - 1 10 Hz
Battery Charge Status 30112 - 1 -
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage 30113 - 1 - V
Battery Current (Charge/Discharge) 30114 - 1 - A
Battery Time Remaining 30115 - 1 - Minutes
Battery Charge Percentage 30116 - 1 - %
Battery Temperature 30117 - 1 - C
Ambient Temperature 30119 - 1 - C
Parallel Load Source 30128 - 1 - -
Rotary Breaker 30129 - 1 - -