Supported Modbus Points
10
Table 9 Liebert NX - Input and Holding Registers
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale Notes / Units
Battery Test Result 30130 - 1 -
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1-L2 30151 - 1 - V
Input Voltage L1 30153 - 1 - V
Input Current L1 30154 - 1 - A
Input Power Factor L1 30155 - 1 100 -
Bypass Voltage L1 30159 - 1 - V
Output Voltage L1 30163 - 1 - V
Output Current L1 30164 - 1 - A
Output Load L1 30165 - 1 1 -
Output Power Factor L1 30166 - 1 100 %
Apparent Output Power L1 30168 - 2 - VA
Reactive Output Power L1 30170 - 2 - VAR
Output Power L1 30172 - 2 - W
Output Current Crest Factor L1 30186 - 1 - %
Input Voltage L2-L3 30201 - 1 - V
Input Voltage L2 30203 - 1 - V
Input Current L2 30204 - 1 - A
Input Power Factor L2 30205 - 1 100 -
Bypass Voltage L2 30209 - 1 - V
Output Voltage L2 30213 - 1 - V
Output Current L2 30214 - 1 - A
Output Load L2 30215 - 1 1 %
Output Power Factor L2 30216 - 1 100 -
Apparent Output Power L2 30218 - 2 - VA
Reactive Output Power L2 30220 - 2 - VAR
Output Power L2 30222 - 2 - W
Output Current Crest Factor L2 30236 - 1 - %
Input Voltage L3-L1 30251 - 1 - V
Input Voltage L3 30253 - 1 - V
Input Current L3 30254 - 1 - A
Input Power Factor L3 30255 - 1 100 -
Bypass Voltage L3 30259 - 1 - V
Output Voltage L3 30263 - 1 - V
Output Current L3 30264 - 1 - A
Output Load L3 30265 - 1 1 %