Supported Modbus Points
24
Table 17 Liebert HiNet - Input and Holding Registers
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale Notes / Units
Number of Input Lines 30004 40004 1 1 Bits 12 - 15
Number of Bypass Lines 30004 40004 1 1 Bits 4 - 7
Number of Output Lines 30004 40004 1 1 Bits 8 - 11
Number of SubModules 30009
40009
1 1
-
Number of Battery Cells 30012
40012
1 1
-
Load (Apparent Power) 30102
-
2 1 VA
Load (Real Power) 30104
-
2 1 W
Input Frequency 30107
-
1 10 Hz
Output Frequency 30108
-
1 10 Hz
Battery Voltage 30113
-
1 1 V
Battery Current (Charge/Discharge) 30114
-
1 1 A
Battery Charge Percentage 30116
-
1 1 %
Ambient Temperature 30119
-
1 1 degrees C
Input Voltage L1 30153
-
1 1 V
Input Current L1 30154
-
1 1 A
Output Voltage L1 30163
-
1 1 V
Output Current L1 30164
-
1 1 A
Input Voltage L2 30203
-
1 1 V
Input Current L2 30204 - 1 1 A
Input Voltage L3 30253 - 1 1 V
Input Current L3 30254 - 1 1 A