Supported Modbus Points
32
Table 23 Liebert Series 300 UPS - Input and Holding Registers
Data Point
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Output Voltage L1 30163 - 1 1 V
Output Current L1 30164 - 1 1 A
Input Voltage L2 30203 - 1 1 V
Input Current L2 30204 - 1 1 A
Bypass Voltage L2 30209 - 1 1 V
Bypass Current L2 30210 - 1 1 A
Output Voltage L2 30213 - 1 1 V
Output Current L2 30214 - 1 1 A
Input Voltage L3 30253 - 1 1 V
Input Current L3 30254 - 1 1 A
Bypass Voltage L3 30259 - 1 1 V
Bypass Current L3 30260 - 1 1 A
Output Voltage L3 30263 - 1 1 V
Output Current L3 30264 - 1 1 A
Black Out Count 30301 - 1 1 -
Brown Out Count 30302 - 1 1 -
Transient Count 30301 - 1 1 -
Silent Audible Alarm - 40101 - - any value
Battery Start - 40102 1 1 1=Start, 0=Abort
Open UPS Output Switch - 40104 - -
Delay time in Seconds, last
digit will be ignored
Reboot UPS Output Switch - 40105 1 1
Delay time in Seconds, last
digit will be ignored
Close UPS Output Switch - 40106 - -
Delay time in Seconds, last
digit will be ignored
Transfer Load to Bypass - 40107 1 1 any value
Transfer Load to Inverter - 40108 any value
Reset UPS Statistic data - 40111 1 1 any value
Turn UPS Outlets On - 40112 1 1
Bitmap mask for Outlet 1-16.
All bits set to 1
will be turned On
Turn UPS Outlets Off - 40113 1 1
Bitmap mask for Outlet 1-16.
All bits set to 1
will be turned Off