User Instructions Section 5877
Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B) Issue AQ, January 15, 2013
Chapter 2. Navigating the MCA Page 2-57
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
MCA Menu
Tree Line No.
(Section
5886)
PCU B#-ID#/N#
RECOGNIZED
or
DSM B#-P#A/B
RECOGNIZED
or
I/O B#-P#
RECOGNIZED
or
CRM B#
RECOGNIZED
or
RCB B#-P#
RECOGNIZED
Lists the last item in the system that was
recognized by the MCA.
GO BACK TO MENU TREE
BEGINNING
Press ENTER to go to the beginning of the
MCA Menu Tree.
NO FUNCTION IN THIS SYSTEM
NO FUNCTION IN THIS SYSTEM
NO FUNCTION IN THIS SYSTEM
NO FUNCTION IN THIS SYSTEM
NO FUNCTION IN THIS SYSTEM
NO FUNCTION IN THIS SYSTEM
############ WAIT ##
V###########
When the system is initially started, an
initialization time and MCA software version
number are displayed.
CHECK VALUES BEFORE
STARTING
Allows you to view (and change) the MCA
settings stored in memory before starting the
system.
1. Press the UP and DOWN ARROWS to
view (change) the following MCA
settings.
Allows you to change the Float Output Voltage
set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
Allows you to change the Test/Equalize Output
Voltage set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
HI VOLTAGE SHUTDOWN
= vv.vvV
Allows you to change the High Voltage
Shutdown set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.