User Instructions Section 5877
Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B) Issue AQ, January 15, 2013
Chapter 2. Navigating the MCA Page 2-15
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
MCA Menu
Tree Line No.
(Section
5886)
MONITORING
INFORMATION
or
Monitoring Info
LED Messages
Status Messages detected by LMS1000.
Status Messages derived from LMS1000 are
displayed by the MCA.
MONITORING DOES NOT
RESPOND
MCA communications with LMS1000 lost.
MCA failed (#### = type of memory failure)
THE CONTROLLER IS
INITIALIZING
System load current above preset adjustable
value (includes distribution loads monitored by
the Distribution Bus Monitoring Circuit Cards
and any MCA I/O Circuit Card set as
"Distribution" [other setting choice is
"Auxiliary"]).
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT aaaaaA
NOW AT aaaaaA
Displays the alarm limit setpoint and the actual
value of the monitored input.
DISTRIBUTION GROUP A
LOAD ALARM
Sum of load currents monitored by all
Distribution Bus Monitoring Circuit Cards set as
Group A designation above preset adjustable
value.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT aaaaaA
NOW AT aaaaaA
Displays the alarm limit setpoint and the actual
value of the monitored input.
DISTRIBUTION GROUP B
LOAD ALARM
Sum of load currents monitored by all
Distribution Bus Monitoring Circuit Cards set as
Group B designation above preset adjustable
value.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT aaaaaA
NOW AT aaaaaA
Displays the alarm limit setpoint and the actual
value of the monitored input.
THE DISPLAY DOES NOT
RESPOND
MCA communications with MCA Display lost.
Press ENTER to go to this menu.
GO BACK TO MENU TREE
BEGINNING
Press ENTER to go to the beginning of the
MCA Menu Tree.
VIEW THE SYSTEM
MEASUREMENTS
Press ENTER to go to this menu.
Comentarios a estos manuales