MCA Menu
Tree Line No.
(Section
5886)
SYSTEM OUTPUT SENSE
vv.vvV (REM)
or
SYSTEM OUTPUT SENSE
vv.vvV (AVG)
The voltage of the external (remote) source
connected to the MCA / Router circuit card (for
MCA alarms and meter reading), if connected.
or
System output sense voltage (average of all
bay's internal sense voltages).
Press ENTER to view individual bay sense
voltages.
ROUTER B# REMOTE
SENSE vv.vvV
External (remote) sense voltage applied to the
MCA / Router Circuit Card, if connected. (B# =
Bay Number).
Press UP and DOWN ARROWS to view other
Router Circuit Cards' sense voltages.
ROUTER B# INTERNAL
SENSE vv.vvV
Internal sense voltage applied to the Router
Circuit Card. (B# = Bay Number).
Press UP and DOWN ARROWS to view other
Router Circuit Cards' sense voltages.
Press ENTER to go to this menu.
GO BACK TO MENU TREE
BEGINNING
Press ENTER to go to the beginning of the
MCA Menu Tree.
Total system load current.
TOTAL DISTRIBUTION
LOAD aaaaaA
or
TOTAL AUXILIARY
LOAD aaaaaA
Total distribution load current (includes
distribution loads monitored by the Distribution
Bus Monitoring Circuit Cards and any MCA I/O
Circuit Card set as "Distribution" [other setting
choice is "Auxiliary"]).
Press ENTER to view individual bay
distribution load currents.
or
Total (sum) load current monitored by MCA I/O
Circuit Cards set as "Auxiliary".
Press ENTER to view individual MCA I/O
circuit card load currents.
DISTRIBUTION GROUP A
LOAD aaaaaA
Total load current monitored by Distribution
Bus Monitoring Circuit Cards set as Group A
designation.
DISTRIBUTION GROUP B
LOAD aaaaaA
Total load current monitored by Distribution
Bus Monitoring Circuit Cards set as Group B
designation.
REMOTE SYSTEM
LOAD aaaaaA
Total Remote Distribution load current reported
by the LMS when LMS Function Channel 63
value is greater than zero.