REMOVING A BATTERY CHARGE DIGITAL TEMPERATURE
COMPENSATION PROBE FROM A PREVIOUSLY OPERATED
SYSTEM
This procedure details the steps to remove a Battery Charge Digital Temperature
Compensation Probe from a system that has been previously started, configured, and
checked.
Procedure
1) In the Configure Menu, set the SLOPE = 0.vvvV C/F to NO TEMPERATURE
COMPENSATION. Temperature Compensation stops and the System returns to
the FLOAT voltage setting.
2) Remove the probe. The Major Alarm activates. Update inventory to clear this
alarm, as described in this chapter.