9. This step is not applicable for FOUNDATION fieldbus. Parameters are
instead entered in the AI-block.
For HART communication, choose Primary Variable, PV.
Fast Key Sequence [1,3,5,1]
Specify the analog output range by setting the Upper Range Value (20
mA) and the Lower Range Value (4 mA) to the desired corresponding
level values.
Fast Key Sequence [1,3,5,2]
The Alarm Mode specifies the output state when a measurement error
occurs. Fast Key Sequence [1,3,5,3]
The following values are used:
High: 21.75 mA (standard) or 22.5 mA (Namur)
Low: 3.75 mA (standard)
Freeze: presents value when error occurs.
Click Next.
10. The Basic Configuration with the Radar Master Wizard is now finished.
Proceed with the Device Specific Setup to see which additional
configuration is needed.
Continue with Steps 2 through 5 in the Guided Setup window:
• Configure thresholds and false echo areas. Fast Key Sequence
[2,1,6,2]
• Restart the device. Fast Key Sequence [2,1,6,4]
• View live values from the device
• Make a complete backup of the device
See the Reference Manual (Document No. 00809-0100-4026) for further
information.