Reference Manual
00809-0600-4026, Rev BA
December 2011
Rosemount Process Radar
2-14
Click Next and the following window appears (Tank Environment).
8. In the Environment window, select Measurement Mode. If the surface is
moving - up or down at rates over 40 mm/s (1.5 in./s), the Rapid Level
Changes box should also be selected. Enter the Upper Product
Dielectric Constant (icons for help functions are available to the right).
For Interface Level with Submerged Probe and Product and
Interface measurement modes, it is important that the dielectric
constant value is exact.
See the Rosemount 5300 Series Reference Manual (Document No.
00809-0100-4530) for details.
Fast Key Sequence [2, 1, 4]
F
OUNDATION fieldbus parameters:
TRANSDUCER 1100>MEAS_MODE
TRANSDUCER 1100
>PRODUCT_DIELEC_RANGE
TRANSDUCER 1100
>UPPER_PRODUCT_DC
TRANSDUCER 1100
>ENV_ENVIRONMENT