Reference Manual
00809-0600-4026, Rev BA
December 2011
Rosemount Process Radar
3-8
Figure 3-7. Presentation of
Analog Output value in
Rosemount Radar Master
For more information, see the Rosemount 5300 Series Reference Manual
(Document No. 00809-0100-4530) section “Viewing Measurement Data In
RRM”.
Verify Analog Output (HART devices only)
Ensure that the loop has been set to manual mode in the DCS for the
applicable transmitter.
Use the transmitter's built-in simulation mode to verify the analog output
settings. Output at least one arbitrary level or interface and verify that the
readings in the DCS match up.
Rosemount Radar Master > Tools > Simulation Mode
Figure 3-8. Simulation Mode
Also, or alternatively, activate the transmitter's loop test function. Output 4, 12,
and 20 mA and verify that the readings in the DCS match up.
Rosemount Radar Master > Output > Analog Out > Loop Test