4-4 / Specifications CI-ControlWaveLP
Figure 4-4
Connectors J12 & J24 - PLD JTAG Headers
Connector J13 - CPU JTAG Header
Connectors J14 & J17 - Manufacturing Test
Figure 4-5 - Connector J15 - Port 80
Table 4-5 - Connector J15 - Port 80 Pin Assignment
Pin # Signal Pin # Signal Pin # Signal Pin # Signal
1 VCC 5 D3 9 D7 13 GND
2 D0 6 D4 10 PWRGOOD 14 N/C
3 D1 7 D5 11 IOW80# - -
4 D2 8 D6 12 ATB.IOW# - -
4.2 COMMUNICATION PORTS
Compatibility: PS/2 (Asynchronous)
Network Port: Port 1, 2. 4,& 5 - RS-232
Port 3 - RS-232 or RS-485
Diagnostic Port: Port 1 recommended for diagnostics & serial recovery.
Baud Rate: 300 to 115K (bps)
Address: Software selectable network address from 1 to 126
Optional Modem: COM4 (J25) & COM5 (J26) Ports may be furnished
with a private line modem (PLM) or a switched network
modem (SNM) board.