Emerson Bristol ControlWave LP Manual de instrucciones Pagina 85

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 166
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 84
CI-ControlWaveLP Service / 3-15
6. Set the ControlWaveLP CPU Switch SW4-8 to the ON position. Restart the
ControlWaveLP to resume normal operation.
Figure 3-10 - Netview Startup Menu - Example with Multiple Networks
3.4.1 Diagnostics Using WINDIAG
All printed circuit boards except the Power Supply/Sequencer Board can be tested using the
WINDIAG program. From WINDIAG’s Main Diagnostics Menu (see Figure 3-11) the
following diagnostic tests can be performed:
CPU & Peripherals Diagnostic: Checks the CPU Board (except for RAM & PROM).
PROM/RAM Diagnostic: Checks the CPU’s RAM and PROM hardware.
Communications Diagnostic: Checks Comm. Ports 1 through 5 - The External loop-
back tests require the use of a loop-back plug.
Analog Output Diagnostic: Checks the Analog Output circuits.
Analog Input Diagnostic: Checks the Analog Input circuits.
Discrete I/O Diagnostic: Checks the DI circuits and/or the DO circuits.
High Speed Counter Diagnostic: Checks the HSC Input circuits.