Precision Cooling
For Business-Critical Continuity™
Liebert
®
Xtreme Density
System Design Manual
Vista de pagina 0
1 2 3 4 5 6 ... 103 104

Indice de contenidos

Pagina 1 - Xtreme Density

Precision CoolingFor Business-Critical Continuity™Liebert® Xtreme Density™System Design Manual

Pagina 2 -

System Description21.2 Generic Piping LayoutsLiebert XD systems are available in two configurations—differentiated essentially by the method of heat r

Pagina 3 - TABLE OF CONTENTS

Specifications and Model Number Nomenclature92Figure 83 Liebert XDP model number nomenclatureRPumpRedundancyXD P 160 – *PumpingunitRevisionlevelModel

Pagina 4

Specifications and Model Number Nomenclature93Notes

Pagina 5

Specifications and Model Number Nomenclature94

Pagina 7

Ensuring The High AvailabilityOf Mission-Critical Data And Applications.Emerson Network Power, the global leader in enabling business-criticalcontinui

Pagina 8

System Description31.3 Liebert XDA—Air Flow EnhancerThe Liebert XDA is a fan unit that boosts the airflow through densely populated enclosures, removi

Pagina 9 - 1.0 SYSTEM DESCRIPTION

System Description41.4 Liebert XDCF—Liebert XD CoolFrameThe Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets

Pagina 10 - 1.2 Generic Piping Layouts

System Description51.5 Liebert XDH—Horizontal Cooling ModuleThe Liebert XDH is designed for placement within a row of computer cabinets in the data ce

Pagina 11 - System Description

System Description61.6 Liebert XDO—Overhead Cooling ModuleThe Liebert XDO is an overhead cooling system designed for installation above heat-dissipati

Pagina 12

System Description71.7 Liebert XDR—Rear Cooling ModuleThe Liebert XDR is a cooling system for high-density heat loads that mounts on the rear of a 24

Pagina 13

System Description81.8 Liebert XDV—Vertical, Above-Cabinet Cooling ModuleThe Liebert XDV cooling system is designed to be attached to the top of a com

Pagina 14

System Description91.9 Liebert XDC—Refrigerant ChillerThe Liebert XDC is an indoor chiller that connects directly to the Liebert XD cooling modules an

Pagina 15

System Description101.10 Liebert XDP—Pumping UnitThe Liebert XDP isolates the building’s chilled water circuit from the pumped refrigerant circuit. Th

Pagina 16

System Description111.11 Liebert XD PipingLiebert XD Piping is prefabricated distribution piping that is installed in anticipation of a growing sys-te

Pagina 18 - Liebert XDP Minimum Load

Starting a New Equipment Cooling Project122.0 STARTING A NEW EQUIPMENT COOLING PROJECT2.1 Determining Cooling Equipment Needs1. Is adequate space avai

Pagina 19 - 1.11 Liebert XD Piping

Starting a New Equipment Cooling Project132.2 Implementing a Hot-Aisle/Cold Aisle DesignA best practice is to place equipment racks in alternating row

Pagina 20

Designing a Liebert XD Solution143.0 DESIGNING A LIEBERT XD SOLUTIONLiebert XD systems are intended for use with precision air conditioning equipment,

Pagina 21

Designing a Liebert XD Solution15ExampleFor example, a 2000 ft2 server room with has 30 racks, 15 racks produce 20kW of heat each and 15 produce 10kW

Pagina 22

Designing a Liebert XD Solution16either Liebert XDH20, Liebert XDO20 or Liebert XDR20. The racks with 10kW per rack could be cooled using the Liebert

Pagina 23

Designing a Liebert XD Solution17Different types of Liebert XD cooling modules may be connected to the same Liebert XDP or Liebert XDC as long as the

Pagina 24

Designing a Liebert XD Solution183.4.2 System Connection ConfigurationIf possible, connect the Liebert XD modules to Liebert XDPs or Liebert XDCs in a

Pagina 25

Designing a Liebert XD Solution193.6 Liebert XDCF PlacementThe Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabine

Pagina 26 - NOT TO SCALE

Designing a Liebert XD Solution203.7 Liebert XDH PlacementThe free-standing Liebert XDH cooling unit is best placed among the equipment cabinets in a

Pagina 27 - 3.6 Liebert XDCF Placement

Designing a Liebert XD Solution213.8 Liebert XDO Placement3.8.1 Determining Spacing of Liebert XDOs in an AisleLiebert XDO units should be placed in r

Pagina 28 - 3.7 Liebert XDH Placement

iTABLE OF CONTENTS1.0 SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11.1

Pagina 29 - 3.8 Liebert XDO Placement

Designing a Liebert XD Solution223.8.2 Determining Vertical Placement of Liebert XDOs Above the Cold AisleIn the maximum density configuration, Emerso

Pagina 30 - Hot air is

Designing a Liebert XD Solution233.9 Liebert XDR Unit PlacementThe Liebert XDR does not require a hot aisle/cold aisle arrangement for effective and e

Pagina 31 - 3.9.1 Airflow

Designing a Liebert XD Solution243.10 Liebert XDV Unit PlacementLiebert XDV units should be placed on top of the cabinets that generate the greatest a

Pagina 32

Designing a Liebert XD Solution253.11 Liebert XDP/Liebert XDC PlacementThe Liebert XDP/Liebert XDC may be placed in the critical space or in an adjace

Pagina 33

Designing a Liebert XD Solution263.12 Examples of Expansion and Interlaced Connection of Liebert XD Cooling ModulesFigure 21 Liebert XDV units mounted

Pagina 34 - Interlaced piping arrangement

Designing a Liebert XD Solution27Figure 23 Liebert XDV units mounted on racks emitting 8kW of heat top viewFigure 24 Liebert XDV units mounted on rack

Pagina 35

Designing a Liebert XD Solution28Figure 25 Multiple Liebert XD modules in an interlaced systemInstalling the Liebert XDR in a hot aisle/cold aisle con

Pagina 36

Designing a Liebert XD Solution293.13 Liebert XD Piping System DesignAll piping must be ASTM (American Society for Testing and Materials) Type “ACR” c

Pagina 37 - Liebert XDC

Designing a Liebert XD Solution30For additional information about piping connections, see the unit’s user manual: Liebert XDP, 16644; Liebert XDC, SL-

Pagina 38 - 3.14 Liebert XD Piping Slope

Designing a Liebert XD Solution313.15 Bypass Flow ControllersTo ensure the XDP/XDC pumps operate within the optimum range, some installations require

Pagina 39 - 3.15 Bypass Flow Controllers

ii3.19 Determining Refrigerant Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 393.19.1 Liebert X

Pagina 40 - Liebert XDP

Designing a Liebert XD Solution32Figure 31 Bypass flow controller pipingFilter Dryer AssemblyLiebert XD CoolingModule #1Liebert XD CoolingModule #2Coo

Pagina 41 - Refer to Table 8

Designing a Liebert XD Solution33Figure 32 Hard-pipe connection diagram for Liebert cooling modules Refer to Table 8 for details.Rear of Liebert XD Co

Pagina 42 - DPN000773

Designing a Liebert XD Solution343.16 Piping Installation Method Prefabricated HeadersThe assembly and connection means used for piping in the Liebert

Pagina 43

Designing a Liebert XD Solution35Figure 34 Four-port prefabricated piping for Liebert XD cooling modulesTable 11 Four-port prefabricated piping legend

Pagina 44

Designing a Liebert XD Solution36Figure 35 Five-port prefabricated piping for Liebert XD cooling modulesTable 12 Five-port prefabricated piping legend

Pagina 45

Designing a Liebert XD Solution37Figure 36 Ten-port prefabricated piping for Liebert XD cooling modulesTable 13 Ten-port prefabricated piping legendBr

Pagina 46 - 3. Bottom Module

Designing a Liebert XD Solution383.17 Liebert XD Flex Pipe KitLiebert XD Flex Pipe kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8,2.4

Pagina 47 - 3.18 Liebert XD Refrigerant

Designing a Liebert XD Solution393.18 Liebert XD RefrigerantThe refrigerant used in the Liebert XD system is HFC-134a (1,1,1,2-tetrafluoroethane), mad

Pagina 48

Designing a Liebert XD Solution40Table 15 System R-134a charge for a Liebert XDP/Liebert XDC with any modelLiebert XDH/Liebert XDO/Liebert XDV/Liebert

Pagina 49

Designing a Liebert XD Solution413.19.2 Calculating Refrigerant R134a Charge—ExampleUsing Tables 15, 16, 17 and 18, calculate the refrigerant charge o

Pagina 50 - Use Copeland

iiiFIGURESFigure 1 Liebert XDP generic piping layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 51 - 3.21 Electrical

Designing a Liebert XD Solution42Figure 37 Additional oil requirements for refrigerant chargeTo calculate the oil required, use the following formula:

Pagina 52 - or Liebert XDV

Designing a Liebert XD Solution433.20 Chilled Water PipingThe Liebert XDP is offered only with a two-way chilled water control valve. Some application

Pagina 53 - Figure 39 Overall dimensions

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV444.0 LIEBERT XD COOLING MODULES—LIEBERT XDCF, LIEBERT X

Pagina 54

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV454.2 Liebert XDCF Mechanical ConsiderationsThe Liebert

Pagina 55 - 4.4.1 Header System

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV464.3 Liebert XDCF Installation ConsiderationsNo cutting

Pagina 56 - Detail “A”

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV474.4.1 Header SystemThe Liebert XDCF module system requ

Pagina 57

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV48• Tie-Down Bracket—An optional tie-down bracket may be

Pagina 58 - RIGHT SIDE

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV494.7 Liebert XDO Standard Features• Micro Channel Heat

Pagina 59

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV50Figure 44 Dimensional data—Liebert XDO hard-piped unit

Pagina 60

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV51Figure 46 Liebert XDO internal mounting locationDPN000

Pagina 61

ivFigure 49 Liebert XDR dimensions with hard-piped connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Figure 50 Liebert

Pagina 62

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV52Figure 47 Top and front electrical access points and t

Pagina 63

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV534.9 Liebert XDR Standard Features• Micro-channel Heat

Pagina 64

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV54Table 26 Cooling capacity, 1500-3000 cfm air flowDegre

Pagina 65

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV55Figure 49 Liebert XDR dimensions with hard-piped conne

Pagina 66

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV56Figure 50 Liebert XDR dimensions with one-shot connect

Pagina 67 - Table 27 Dimensional data

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV57Figure 51 Liebert XDR dimensions with removable connec

Pagina 68 - Detail Area “A”

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV584.12 Liebert XDV Standard Features• Micro Channel Heat

Pagina 69

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV59Figure 52 Liebert XDV dimensions Table 27 Dimensional

Pagina 70

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV60Figure 53 Liebert XDV dimensions with one-shot connect

Pagina 71 - DPN000768

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV61Figure 55 Suspending single Liebert XDV from the roof

Pagina 72 - AB C D E F G

vTable 12 Five-port prefabricated piping legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36Tabl

Pagina 73

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV62Figure 56 Alternative mounting methods—mounting multip

Pagina 74 - 10-1/2"

Liebert XDC and Liebert XDP635.0 LIEBERT XDC AND LIEBERT XDP5.1 Liebert XDC Standard Features• Compressors—Scroll with a suction gas cooled motor, vib

Pagina 75 - Not Shown for Clarity

Liebert XDC and Liebert XDP64Figure 58 Liebert XDC piping locationsTable 29 Liebert XD Chiller piping connection sizesAir Cooled Models Piping Outlet

Pagina 76

Liebert XDC and Liebert XDP65Figure 59 Positioning a water/glycol Liebert XDC for placement on a floor standTable 30 Liebert XDC Water/Glycol Piping C

Pagina 77

Liebert XDC and Liebert XDP66Figure 60 Piping locations—floor stand and valve assemblyShaded areas indicate a recommendedclearance of 36" (915mm)

Pagina 78 - Electrical handy box

Liebert XDC and Liebert XDP67Figure 61 Front view of Liebert XDC and electrical enclosuresFigure 62 Liebert XDC electrical enclosure knockout location

Pagina 79

Liebert XDC and Liebert XDP68Figure 63 Liebert XDC high-voltage connections—primary disconnect switch, 60Hz modelsFigure 64 Liebert XDC high-voltage c

Pagina 80

Liebert XDC and Liebert XDP69Figure 65 Liebert XDC high-voltage connections—secondary disconnect switch, 60Hz modelsFigure 66 Liebert XDC high-voltage

Pagina 81 - 16-1/8"

Liebert XDC and Liebert XDP70Figure 67 Liebert XDC heat rejection electrical connection pointsFigure 68 Liebert XDC electrical enclosure knockout loca

Pagina 82 - Knockout

Liebert XDC and Liebert XDP71Figure 69 Liebert XDC Extra Low Voltage field-connection pointsControl wiring must be Class 2 and installedin accordance

Pagina 84

Liebert XDC and Liebert XDP725.2 Liebert XDP Standard Features• Heat Exchanger—Brazed plate design with interwoven circuiting constructed of stainless

Pagina 85 - XD 10 B *

Liebert XDC and Liebert XDP73Figure 71 Liebert XDP piping access points and external featuresTable 32 Unit piping outlet connection sizes, inches, OD

Pagina 86 - Number of Fans

Liebert XDC and Liebert XDP74Figure 72 Front view of Liebert XDP and electrical enclosureFigure 73 Liebert XDP electrical enclosure knockout location

Pagina 87

Liebert XDC and Liebert XDP75Figure 74 Liebert XDP electrical enclosure knockout locations for field wiringFigure 75 Liebert XDP high-voltage connecti

Pagina 88 - XD H 32 B K —

Liebert XDC and Liebert XDP76Figure 76 Liebert XDP high-voltage connections—50HzBusbarCustomer PowerConnectionPump CircuitBreakersPump ContactorsGroun

Pagina 89

Specifications and Model Number Nomenclature776.0 SPECIFICATIONS AND MODEL NUMBER NOMENCLATUREFigure 77 Liebert XDCF model number nomenclatureTable 33

Pagina 90

Specifications and Model Number Nomenclature78Table 34 Liebert XDH20 specificationsModelsXDH20BK1XDH20SK1(60Hz)XDH20BS1XDH20SS1(50/60Hz)Cooling Capaci

Pagina 91 - Example: XDO20BK– –*

Specifications and Model Number Nomenclature79Table 35 Liebert XDH32 specificationsModelsXDH32BK1XDH32SK1(60Hz)XDH32BS1XDH32SS1(50/60Hz)Cooling Capaci

Pagina 92 - Example: XDR20B1R — *

Specifications and Model Number Nomenclature80Figure 78 Liebert XDH model number nomenclatureXD H 32 B K —Horizontal row coolerK = 120V-1ph-60HzS = 20

Pagina 93

Specifications and Model Number Nomenclature81Table 36 Liebert XDO16 specificationsModelsXDO16BK1XDO16SK1(60Hz)XDO16BS1XDO16SS1(60Hz)XDO16BS1XDO16SS1(

Pagina 94

System Description11.0 SYSTEM DESCRIPTIONThe Liebert XD™ family of cooling units delivers efficient, sensible cooling to high-heat environ-ments. Lieb

Pagina 95 - XD V B K —

Specifications and Model Number Nomenclature82Table 37 Liebert XDO20 specificationsModelsXDO20BK1XDO20SK1XDO20BS1XDO20SS160Hz 60Hz 50HzCooling Capacit

Pagina 96

Specifications and Model Number Nomenclature83Figure 79 Liebert XDO model number nomenclatureTable 38 Options for Liebert XDO20 and Liebert XDO16Optio

Pagina 97

Specifications and Model Number Nomenclature84Figure 80 Liebert XDR model number nomenclatureTable 40 Liebert XDR20 specificationsModelsXDR20B1- *XDR2

Pagina 98 - XD C 160 – *

Specifications and Model Number Nomenclature85Table 42 Liebert XDV8 specificationsModelsXDV8BK1XDV8SK1XDV8BT1XDV8ST1XDV8BS1XDV8SS160 Hz 60 Hz 50 Hz 50

Pagina 99

Specifications and Model Number Nomenclature86Table 43 Liebert XDV10 specificationsModelsXDV10BK1XDV10SK1XDV10BT1XDV10ST1XDV10BS1XDV10SS160 Hz 60 Hz 5

Pagina 100 - XD P 160 – *

Specifications and Model Number Nomenclature87Figure 81 Liebert XDV model number nomenclatureTable 44 Liebert XDV dimensions—domestic and exportModelS

Pagina 101

Specifications and Model Number Nomenclature88Table 45 Liebert XDC160 specificationsModelsXDC160 Air XDC160 Water / GlycolXDC160AA XDC160AM189192G3 (9

Pagina 102

Specifications and Model Number Nomenclature89Table 46 Floor stand specifications—water-cooled Liebert XDCXDC160 Water Floor Stand - 60Hz189192G518919

Pagina 103

Specifications and Model Number Nomenclature90Figure 82 Liebert XDC model number nomenclatureTable 48 Floor stand specifications—Liebert XDC with 40%

Pagina 104 - SL-16655_REV10_10-09

Specifications and Model Number Nomenclature91Table 49 Liebert XDP160 specificationsModelsXDP160RC--3 XDP160RA--3 XDP160RM--3Cooling Capacity, Nominal