Installation and Use Manual 21
Installation and Setup
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin
2.7 Obtain and configure a site key
To obtain and configure a site key:
1. Open the License Request file as follows:
Start > Programs > MMI > ProLink II v2.9 > ProLink II License Request Form
2. Edit the file, supplying all requested information including the site code.
To find the site code, choose
File > License (see Figure 2-13).
3. Save the edited file.
4. Contact Micro Motion in one of the following ways:
• Send an email to:
Flow.Support@Emerson.com
Attach the edited file to the email. The file is named LicenseRequest.txt, and in typical
installations is located in
Program Files > MMI > ProLink II v2.9.
Note: This is the default location. If the ProLink II installation program found an existing license file,
the program and License Request file were installed in the location of the license file.
• Telephone 800-522-6277 (toll-free in the U.S.), or 303-530-8250 (worldwide), and request
a site key. Have the edited registration text file available for reference.
Note: To minimize the possibility of error, Micro Motion recommends using the email method.
5. When the site key is provided:
a. Start ProLink II.
b. Choose
File > License. See Figure 2-13.
Table 2-6 Default communication parameters for RFT97xx and IFT97xx transmitters
Default values
Transmitter Physical layer Protocol Baud Data bits
(1)
(1) ProLink II automatically sets data bits appropriately for the configured protocol. Even though a data bits parameter may be
configured in the transmitter, you do not need to configure it in ProLink II.
Stop bits Parity Address
IFT9701/9703
(2)
(2) IFT9701/9703 communication parameters are not configurable. The settings shown here are always in effect.
Bell 202
(3)
(3) Connection to primary mA output.
HART 1200 8 1 odd 0
RFT9712 Bell 202
(3)
HART 1200 8 1 odd 0
RS-485
(4)
(4) Connection to RS-485 terminals.
HART 1200 8 1 odd 0
RFT9739 v2 Bell 202
(3)
HART 1200 8 1 odd 0
RS-485
(4)
HART 1200 8 1 odd 0
RFT9739 v3 Bell 202
(3)
HART 1200 8 1 odd 0
RS-485
(4)(5)
(5) Dip switch settings on the transmitter are used to select either Std. comm or User defined.
• Std. comm Modbus RTU 9600 8 1 odd 1
• User defined HART 1200 8 1 odd 0