Emerson Network Router Manual de usuario Pagina 20

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 96
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 19
14 ProLink
®
II Software for Micro Motion
®
Transmitters
Installation and Setup
Figure 2-5 Model 1700/2700 I.S. transmitters: Resistance and voltage requirements for
HART/Bell 202 connections
Figure 2-6 HART/RS-485 connection to transmitter or multidrop network
R
max
= (V
supply
– 12)/0.023
A minimum of 250 ohms and 17.5 volts is required
Supply voltage VDC (Volts)
External resistance (Ohms)
Operating range
12 3014 16 18 20 22 24 26 28
0
1000
900
800
700
600
500
400
300
200
100
DCS or
PLC
R1
Attach serial port or USB
adapter if necessary (not
shown)
RS-485 terminals
Transmitter
RS-232 <-> 2-wire RS-485
interface converter
Notes:
Connect the interface leads to the RS-485 terminals on the transmitter, or to any point on the network.
Ensure that your transmitter’s RS-485 terminals are configured for HART protocol.
For RFT9712 transmitters, set the jumper for RS-485 communications.
For long-distance communication, or if noise from an external source interferes with the signal, add two 120-Ω
terminating resistors (R1) at each end of the RS-485 network.
Vista de pagina 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 95 96

Comentarios a estos manuales

Sin comentarios