Instruction Manual Supplement
D103638X012
DVC6200 SIS Digital Valve Controller
August 2014
26
Published Data, used for the Gateway’s OPC and Modbus outputs, falls into the following categories:
Field Device Identification Values:
Values that define the identity of the DVC6200 SIS. These include:
D MANUFACTURER (for “Fisher Controls” the value is “19”)
D DEVICE_TYPE
D DEVICE_REVISION
D HARDWARE_REVISION
D SOFTWARE_REVISION
D DEVICE_ID
D UNIVERSAL_REVISION (HART version)
D REQUEST_PREAMBLES
D RESPONSE_PREAMBLES
Variable information:
The Gateway receives updates concerning the DVC6200 SIS’s configured device variables. The information for any
given device variable is displayed by:
1. Dynamic Variable indicator (“PV”, “SV”, etc.)
2. The Device Variable ID number assigned to that Dynamic Variable
3. By the Device Variable Name (only if the Gateway has version 4.4 firmware or later)
Dynamic Variable Device Variable ID Device Variable Name(s)
Analog Input PV 0* ANALOG_INPUT
Internal Temperature 1 INTERNAL_TEMPERATURE
Pressure TV 2* PRESSURE_PORT_A
Travel 3 TRAVEL
Drive Signal 4 DRIVE_SIGNAL
Pressure 5 PRESSURE_PORT_B
Travel Setpoint 6 TRAVEL_SETPOINT
Pressure 7 DIFFERENTIAL_PRESSURE
Pressure 8 SUPPLY_PRESSURE
Implied Valve Position SV 9* IMPLIED_VALVE_POSITION
Travel QV 10* PRIMARY_FEEDBACK
Milliamp Current 245 CURRENT
*Default Value indicated