Instruction Manual Supplement
D103638X012
DVC6200 SIS Digital Valve Controller
August 2014
23
Annex A Compatibility Checklist
Manufacturer, Model, and Revision Fisher Controls DVC6200 SIS Device Revision 2
Device Type Pneumatic Control Valve Positioner
HART Protocol Revision 7.4
User switchable between HART 5 mode and
HART 7 mode?
Yes, either with configuration within DD or with a special
string in the Message field.
Device Description Available?
Device Revision 1 is for HART 5 mode.
Device Revision 2 is for HART 7 mode.
Number and type of process connections None
Number of host connections
Input: Control signal to Loop ± terminals
Output: Transmitter or Switch from Out ± terminals
Number of Dynamic Variables 4
Mappable Dynamic Variables? Yes. SV, TV, and FV are mappable. PV is not.
Number of Device Variables 13
Number of Supported Common Practice
Commands
10
Burst Mode?
In HART 7 mode: No
In HART 5 mode: Yes
Capture Device Variables? No
Write Protection? Yes