D7.21.2/1011/E
17/17
Trip: Appears when there is a low
compressor voltage.
Supply voltage is not in the
specified range.
Loose wiring connections at the
terminal plate.
Worn out contactors.
Faults with other peripheral
electrical loads.
Verify voltage supply from the main buss.
Verify voltage into and out of contactor (repair or replace contactor if necessary).
Measure voltage at the compressor terminal (refer to AE10-1244, Recommended
Contactor Selection for 3-Phase Motor Control – Power Supply Problems).
Verify that motor electrical connections are tight at the compressor.
Verify that there are not any faults with other peripheral electrical loads (for example
fan motors).
Trip: Appears when the voltage
imbalance value exceeds the set
value (default 5%).
Loose wiring connections at the
compressor terminal plate inside T-
Box.
Worn out contactors.
Faults with other peripheral
electrical loads.
Single phasing conditions.
Verify voltage supply from the main buss.
Verify voltage into and out of contactor (repair or replace contactor if necessary).
Measure voltage at the compressor terminal (refer to AE10-1244, Recommended
Contactor Selection for 3-Phase Motor Control– Power Supply Problems).
Verify that motor electrical connections are tight at the compressor.
Verify that there are not any faults with other peripheral electrical loads (for example
fan motors).