Technical Information
D7.21.2/1011/E
13/17
5 CoreSense Diagnostics jumper settings
The last compressor in the daisy-chain must be “terminated” by moving the jumper from JP5 to JP3. For all other
compressors the jumper should remain in the default JP5 position.
JP4 should be set “1-2” if connected to an iPro rack controller. Set JP4 to “2-3” for other pack controllers.
Do not remove JP1. This is reserved for future use.
Figure 13
6 CoreSense Diagnostics DIP-Switch setting
Figure 14: CoreSense Diagnostics DIP-Switch setting