Secondary Heat Source 48RLXFZ(1)
In locations where weather conditions exceed the operating range of
the outdoor unit, model AOU48RLXFZ, there is an easy way to integrate
an automated heating system changeover circuit so that a secondary
heating source can be brought ON seamlessly. By adding a third party
device and using the emergency stop function, you are able to shut the
system off and turn on a secondary heat source when outdoor ambient
falls below operating ranges. A wire kit part number UTY-XWZXZ3 is
required to use this function, along with a third party device. Fujitsu
tested this function using the following control:16E09-101 Emerson
Universal electronic temperature control.
UTY
-
XWZXZ3
NOTE: The system will have to be turn on manually by a remote once the
ambient temperatures are within operating range.
Caution: Turn off
power when making
wire connections.
NOTE You need to use
function F2 mode.
Function number 20,
setting number 01.
I/O connector CN934.
For instruction on
setting functions refer
to the install manual.
UTY
-
XWZXZ3
In order to perform some of these tests an electrical and/or refrigerant license is required. We strongly advise to
check the Service manual for more detailed explanation. If you are not sure about these recommendations please
contact us at 866-952-8324.
Tech-Tip #035
Rev. Date 1/30/14