2
Types 1098-EGR and 1098H-EGR
piLot tYpes
outLet (controL) pressure range
6351
0,21 to 1,38
0,34 to 2,41
2,41 to 6,90
3 to 20
5 to 35
35 to 100
6352
35 mbar to 0,14 bar
0,14 to 0,69
14-inches w.c. to 2 psig
2 to 10
6353
0,21 to 2,76
2,41 to 8,62
3 to 40
35 to 125
6354L
(1)
6354M
(2)
6354H
5,86 to 13,8
12,1 to 15,2
13,8 to 20,7
85 to 200
175 to 220
200 to 300
61L
61LD
61LE
0,02 to 0,14
0,07 to 0,34
0,14 to 0,69
0,34 to 1,03
0,69 to 1,38
0.25 to 2
1 to 5
2 to 10
5 to 15
10 to 20
61H 0,69 to 4,48 10 to 65
61HP
1,03 to 3,10
2,41 to 6,90
6,90 to 20,7
15 to 45
35 to 100
100 to 300
Y600AM
10 to 20 mbar
17 to 40 mbar
37 to 83 mbar
0,83 to 0,17
0,17 to 0,31
0,31 to 0,48
4 to 8-inches w.c.
7 to 16-inches w.c.
15-inches w.c. to 1.2 psig
1.2 to 2.5
2.5 to 4.5
4.5 to 7
1. Without diaphragm limiter.
2. With diaphragm limiter.
Table 2. Outlet Pressure Ranges
actuator
outLet
(controL)
pressure
emergencY
casing
pressure
1098
30
40 (standard)
70
6,90
5,17
3,45
100
75
50
7,93
5,65
4,48
115
82
65
1098H 30 24,1 350 27,6 400
Table 3. Actuator Sizes and Maximum Pressures
BodY sizes
spring part numBer
and coLor
maximum aLLoWaBLe
/
(1)
minimum differentiaL pressure
dn nps
25 1
14A9687X012, Green 4,14 / 60 0,24 3.5 0,17 2.5 0,07 1
14A9680X012, Blue 8,62 / 125 0,34 5 0,21 3 0,10 1.5
14A9679X012, Red
27,6 / 400 or body rating limit,
whichever is lower
0,48 7 0,34 5 0,17 2.5
50 2
14A6768X012, Yellow 1,38 / 20 - - - - - - - - - - - - - - - - 0,07 1
14A6626X012, Green 4,14 / 60 0,28 4 0,21 3 0,10 1.5
14A6627X012, Blue 8,62 / 125 0,41 6 0,34 5 0,14 2
14A6628X012, Red
27,6 / 400 or body rating limit,
whichever is lower
0,76 11 0,69 10 0,21 3
80 3
14A6771X012, Yellow 1,38 / 20 - - - - - - - - - - - - - - - - 0,07 1
14A6629X012, Green 4,14 / 60 0,34 5 0,28 4 0,14 2
14A6630X012, Blue 8,62 / 125 0,55 8 0,41 6 0,17 2.5
14A6631X012, Red
27,6 / 400 or body rating limit,
whichever is lower
0,97 14 0,76 11 0,28 4
100 4
14A6770X012, Yellow 1,38 / 20 - - - - - - - - - - - - - - - - 0,09 1.3
14A6632X012, Green 4,14 / 60 0,69 10 0,34 5 0,17 2.5
14A6633X012, Blue 8,62 / 125 0,90 13 0,55 8 0,21 3
14A6634X012, Red
27,6 / 400 or body rating limit,
whichever is lower
1,52 22 0,90 13 0,34 5
150,
200 x 150,
300 x 150
6,
8 x 6,
12 x 6
15A2253X012, Yellow 1,38 / 20 - - - - - - - - - - - - - - - - 0,15 2.2
14A9686X012, Green 4,14 / 60 0,90 13 0,66 9.5 0,28 4
14A9685X012, Blue 8,62 / 125 1,31 19 0,97 14 0,41 6
15A2615X012, Red
27,6 / 400 or body rating limit,
whichever is lower
1,93
(2)
28
(2)
1,31 19 0,55 8
1. Maximum inlet pressure is equal to set pressure plus maximum differential.
2. Requires special 6300 Series pilot construction without integral relief valve and with external Type 1806 2,76 bar d / 40 psid relief valve.
Table 4. Maximum and Minimum Differential Pressures for Main Valve Selection
The recommended pressure limitations are stamped on
the regulator nameplate. Some type of overpressure
protection is needed if the actual inlet pressure
exceeds the maximum operating outlet pressure rating.
Overpressure protection should also be provided if the