R600 and HSRL Series LP-Gas RegulatorsD450133T012Instruction ManualMCK 2141February 2013www.fisherregulators.comR600 and HSRL Series Instruction Manua
R600 and HSRL Series LP-Gas Regulators2SpecicationsPressure Taps Size RestrictionR600 Series: 1/8 NPT: #54 (0.055 inch / 1.40 mm) Drill on outlet and
R600 and HSRL Series LP-Gas Regulators3TYPETYPICAL SETPOINTNOMINAL RELIEF VALVE START-TO-DISCHARGEMAXIMUM INLET PRESSURE TO NOT EXCEED OUTLET PRESSURE
R600 and HSRL Series LP-Gas Regulators4• Replace old pigtails. Blow out any debris, dirt or copper sulfate in the copper tubing and the pipeline. •
R600 and HSRL Series LP-Gas Regulators5Figure 3. Tank InstallationFigure 4. Basement InstallationVENT OPENING MUST BE AT LEAST 3 FEET / 0.91 meter H
R600 and HSRL Series LP-Gas Regulators6Meter InstallationsType R642 regulators have an angle body that makes it easy to install on to a gas meter inst
R600 and HSRL Series LP-Gas Regulators7Make sure the regulator’s closing cap is on tightly, and maintain drainage away from the dome at all times.Adju
©Emerson Process Management Regulator Technologies, Inc., 2001, 2013; All Rights ReservedR600 and HSRL Series LP-Gas RegulatorsThe Emerson logo is a t