Fisher ROC Serial Driver Help
Possible Cause:
The import file is corrupt.
Solution:
In the server project, right-click on the device and then select Properties. Then, open the Tag Import Settings
tab to review the settings and check the import file. If necessary, re-export the project file from within
ROCLINK800.
See Also:
Tag Import Settings
Automatic Tag Database Generation
Unable to generate a tag database for device '<device>'. Reason: Input file not
found
Error Type:
Warning
Possible Cause:
The import file cannot be found.
Solution:
In the server project, right-click on the device and then select Properties. Then, open the Tag Import Settings
tab to check the name of the project file that will be imported. This file must be accessible to the server's
Runtime.
See Also:
Tag Import Settings
Automatic Tag Database Generation
Unable to generate a tag database for device '<device>'. Reason: Low memory
resources
Error Type:
Warning
Possible Cause:
The memory required for Automatic Tag Generation could not be allocated. The process is aborted.
Solution:
Close unused applications and/or increase the amount of virtual memory and try again.
Unable to generate a tag database for device '<device>'. Reason: ROC system
file <file name> not found
Error Type:
Warning
Possible Cause:
The ROC system file cannot be found.
Solution:
Ensure that the ROC system file (*.mdb) is present in the location specified in the Tag Import Settings tab of
Device Properties. This file must be accessible to the server's Runtime.
Unable to generate a tag database for device '<device>'. Reason: System DB
file <file name> not found
Error Type:
Warning
Possible Cause:
www. kepware.com
25