50
Rosemount 3051
September 2014
www.rosemount.com
Service
Liquid, gas, and vapor applications
4-20 mA HART (output code A)
Power supply
External power supply required. Standard transmitter (4-20mA)
operates on 10.5-42.4 Vdc with no load
Load limitations
Maximum loop resistance is determined by the voltage level of
the external power supply described by:
Indication
Optional two line LCD/LOI Display
Optional configuration buttons
Configuration buttons need to be specified:
Digital Zero trim (option code DZ) changes digital value of the
transmitter and is used for performing a sensor zero trim.
Analog Zero Span (option code D4) changes analog value and
can be used to rerange the transmitter with an applied pressure.
Output
Two-wire 4-20mA, user selectable for linear or square root
output. Digital process variable superimposed on 4-20 mA
signal, available to any host that conforms to HART protocol.
The 3051 comes with Selectable HART Revisions. Digital
communications based on HART Revision 5 (default) or Revision
7 (option code HR7) protocol can be selected. The HART revision
can be switched in the field using any HART based configuration
tool or the optional local operator interface (M4).
Power advisory diagnostics
Power Advisory Diagnostics pro-actively detect and notify
you of degraded electrical loop integrity before it can affect
your process operation. Example loop problems that can be
detected include water in the terminal compartment,
corrosion of terminals, improper grounding, and unstable
power supplies.
The Device Dashboard presents the diagnostics in a
graphical, task-based interface that provides single-click
access to critical process/device information and descriptive
graphical troubleshooting.
Local operator interface
The LOI utilizes a 2 button menu with internal and external
configuration buttons. Internal buttons are always
configured for Local Operator Interface. External Buttons can
be configured for either LOI (option code M4), Analog Zero
and Span (option code D4) or Digital Zero Trim (option code
DZ). See Rosemount 3051 product manual
(00809-0100-4007) for LOI configuration menu.
FOUNDATION fieldbus (output code F)
Power supply
External power supply required; transmitters operate on 9.0 to
32.0 V dc transmitter terminal voltage. FISCO transmitters
operate on 9.0 to 17.5 V dc.
Current draw
17.5 mA for all configurations (including LCD display option)
Indication
Optional two line LCD display
FOUNDATION fieldbus block execution times
F
OUNDATION fieldbus parameters
F
OUNDATION fieldbus function blocks (option A01)
Resource block
The resource block contains diagnostic, hardware, and
electronics information. There are no linkable inputs or
outputs to the Resource Block.
Sensor transducer block
The sensor transducer block contains sensor information
and the ability to calibrate the pressure sensor or recall
factory calibration.
Communication requires a minimum
loop resistance of 250 ohms.
(1) For CSA approval, power supply must not exceed 42.4 V.
Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5)
Voltage (Vdc)
Load (s)
Operating
Region
1387
1000
500
0
10.5 20 30
42.4
(1)
Block Execution time
Resource N/A
Sensor and SPM Transducer N/A
LCD Display N/A
Analog Input 1, 2 20 milliseconds
PID 25 milliseconds
Input Selector 20 milliseconds
Arithmetic 20 milliseconds
Signal Characterizer 20 milliseconds
Integrator 20 milliseconds
Output Splitter 20 milliseconds
Control Selector 20 milliseconds
Links 25 (max.)
Virtual Communications Relationships (VCR) 20 (max.)